To prevent the risk of fire, the structures surrounding the stove must be protected from the heat.
Floors in wood or in any flammable material must be suitably protected at the base with steel or toughened glass
panels; the protection must cover the base and also a certain area in front of the stove.
Any wooden boards or beams above or crossed by the flue must be suitably protected in conformity with the
requirements of the specific current installation standards.
The minimum front distance for the protection of flammable objects is 1.5 m. The minimum safety distances from
flammable materials must comply with the following table:
Every installation must provide for an easily accessible technical space for periodical maintenance.
The stove is provided with 4 adjustable feet to facilitate positioning on not perfectly flat floors. To adjust the height,
tilt the stove slightly and turn the feet as required.
The stove is supplied with the ambient sensor fixed through a wrapper on the back of the stove; we recommend to
remove the wrapper and to locate the sensor in the best position possible as to improve the temperature registration
in accordance with the ambient context and the length of the cable.
As for temperature registration done at a certain distance we reccomend to install the ambient thermostat/ambient
programming clock-thermostat – see. par.4.8.
- The stove cannot be installed in bedrooms, bathrooms and in general in rooms where
another heating unit is already installed without an independent air inflow.
- With wooden floors, install a floor protection base in conformity with the current regulations.
- Suitable fire-prevention devices should be arranged for any eventuality.
- Do not install the stove in places with an explosive atmosphere.

2.3 Air inlet

The stove air inlet pipe or intake is located at the back and is round and 50 mm in diameter.
A quantity of air at least equal to that necessary for combustion must flow in the room where the stove is installed;
therefore the combustion air necessary to ensure correct operation of the stove must be drawn:
from the room, provided there is a wall air inlet near the stove, communicating with the outside and of minimum
area 100 cm² suitably protected externally by a grille;
or with direct connection to the outside with an appropriate pipe having a minimum internal diameter of 50 mm
and maximum length of 1.5 m, provided with antiwind protection at the end (down bend).
Antiwind grille
Flue
Flue connection
Inspection door on
flue
Air inlet
min. 100 cm²
T union with
inspection cap
Floor protection base
40
A = 300 mm
B = 200 mm
C = 1500 mm
D = 200 mm
EASY CRONO HR