CAUTION
Work on gas carrying parts may ONLY be carried out by
qualified, competent individuals.
Adjusting the carbon dioxide setting
IMPORTANT
Only adjust the CO
sure the adjustment is necessary. No adjustments may be made to the gas
valve without prior permission from your
local Daikin distributor. In Belgium, the gas valve may NOT be adjusted and/or
the seal may NOT be removed or broken. Contact your distributor.
1
Remove the cap (A) which covers the adjuster screw.
2
Turn the screw (B) to the right to increase the CO
decrease it. See the following table for the desired value.
Measured value at
Set values CO
maximum power
Natural gas 2H
(G20, 20 mbar)
10.8
10.6
10.4
10.2
10
9.8
9.6
9.4
9.2
9.0
8.8
8.6
3
After measuring the CO
percentage and adjusting the setting, replace the cover
2
cap and the cap of the sample point. Make sure they are gas tight.
4
Select the High setting by twice pressing the
A capital letter will appear on the service display.
5
Measure the CO
percentage. If the CO
2
values in the table which indicates the CO
contact your local distributor.
6
Press + and - simultaneously to leave the test program.
7
Return the front panel to its place.
Daikin Europe NV
setting when you have first checked it and you have made
2
percentage, and to the left to
2
(%) at minimum power (front lid open)
2
Propane 3P
(G31,30/50/37 mbar)
-
9.0±0.1
8.9±0.1
8.8±0.1
8.7±0.1
8.6±0.1
8.5±0.1
and
buttons simultaneously.
percentage still deviates from the
2
percentage at maximum power,
2
10.5±0.1
10.3±0.1
10.1±0.1
9.9±0.1
9.8±0.1
9.6±0.1
-
B
A
03010102
44