Electrical Connections; Mechanical Installation - IMO iDrive-EDX Guide D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Nomenclature
Do not inspect components unless the lamp is off
CAUTION
See manual for correct installation and operation
Model:
EDX-040-21-E
INPUT:
AC 1 phase 50 / 60Hz
OUTPUT:
AC 3 phases 0 – 200Hz
IP20 / UL Open Type (rated -10˚C to 50˚C Ambient)
IMO Precision Controls Ltd
WARNING: THIS PRODUCT MUST BE EARTHED!
EDX
-
040
-
2
iDrive
Power (kW)
0.2
020
0.4
040
0.75
075
1.5
150
2.2
220
100V
1
200V
2
400V
4

Mechanical installation

Standard IP20 type iDrive EDX is designed to be mounted inside a grounded steel enclosure.
The ambient temperature inside the enclosure must not exceed 50˚C or the lifetime of iDrive may be
reduced and manufacturers warranty voided.
If necessary use additional cooling fans and filtered ventilation ports in the enclosure.
Installation must be upright, mounting onto a grounded steel back plate.
Fixing can be via the 4 mounting holes / slots or onto standard DIN rail using the built-in DIN rail clip.
4
Motor Rating: 0.5HP / 0.4KW
VOLTAGE:
200 – 240V (+10%, -15%)
VOLTAGE:
0 - V
IN
1
-
E
Enclosure
IP65 + water &
N4S
dust proof switch
IP65 without water &
N4
dust proof switch
IP20
No Filter
E
EMC Filter built in
1
1Phase
3
3 Phase
I
: 5.4A
RMS
I
: 3.1A
RMS
Power terminals
1Ø 100-120V
1/3Ø 200-240V
3Ø 380-480V
NPN common
Multi function
digital input
12/24Vdc
PNP common
Multi function analogue input
• Set speed
• PID feed
back input
Note 1:
Connect point x to either :-
Terminal 3 (internal +24VDC) for PNP mode (positive switching) OR
Terminal 8 (Common 0V) for NPN mode (negative switching)
Note 2:
External 24VDC may be used to supply the external contacts at point 'x'
If so then connect the 0V of the external supply to Common (terminal 8)

Electrical connections

Braking Unit
(optional)
L1 (L)
L2
L3 (N)
PE
(3) 24V
(4) S1
(5) S2
'x'
(6) S3
(7) S4
(8) COM
(9) +10V
(10) AIN
10kΩ
(11) COM
FM
(12) FM+
T1
T2
Motor
T3
PE
RA (1)
Multi function
RB (2)
relay output
SW1: digital signal
selection (NPN/PNP)
1 2
SW2: control signal
selection (0-10V/4-20mA)
• Option interface
• Multi function I/O
S5
card (2 in, 1 out)
S6
• Remote Keypad
T+
T-
24V/0.6A
5

Publicité