EMOTE MAINTENANCE BYPASS CONNECTION
Note
It is essential to connect the "SERVICE BYPASS" terminal (see "Views of the UPS connections") to the
auxiliary contact of the SERVICE BYPASS switch. The closure of the SERVICE BYPASS switch will open this
auxiliary contact which informs the UPS that the maintenance bypass has been inserted. The absence of this
connection may interrupt the power supply to the load and damage the UPS.
-
-
-
REMOTE MAINTENANCE BYPASS INSTALLATION DIAGRAM
"remote maintenance bypass"