ONNECTIONS OF THE MODEL WITH SEPARATE BYPASS
The very first connection to be carried out is that of the protection conductor (earth cable), which must
be connected to the terminal marked PE. The UPS must not operate without being connected to an
earthing system
THE INPUT AND THE BYPASS NEUTRALS MUST ALWAYS BE CONNECTED.
THE INPUT AND BYPASS LINES MUST REFER TO THE SAME NEUTRAL POTENTIAL.
DO NOT CONNECT THE OUTPUT NEUTRAL TO THE INPUT OR BYPASS NEUTRAL.