Télécharger Imprimer la page

Coelbo SPEEDBOX 1006 MT Mode D'emploi page 12

Masquer les pouces Voir aussi pour SPEEDBOX 1006 MT:

Publicité

Les langues disponibles

Les langues disponibles

START UP (SINGLE DEVICE).
Be sure that the pump is correctly primed
n
Connect the SPEEDBOX to the electric supply with the magnetothermic switch, FAILURE led light will be ON. Wait for 10 seconds while
n
the SPEEDBOX is doing the autotest. Once it finishes, led light FAILURE is OFF and led light LINE is ON. The LCD screen will show
message "SPEEDBOX " and inmediately the language display of the configuration mode.
The device is ready for being configured.
n
START UP (2 DEVICES ASSEMBLY).
M
If we wish to mount 2 devices for working in groups, previous point should be exactly followed - the order of connection is irrelevant. During
the configuration process we will be able to choose which device is the MASTER.
CONFIGURATION. Using pq we can change the values and press ENTER for validation. Whenever we want to quit the
configuration sequence press MENU. After every ENTER it will appears automatically the different screens that constitute the
configuration sequence.
P s e t
4 ,
P b a r
3 ,
L A N G U A G E
E N G L
I S H
M A X .
I N T
1 0
A
R O T A T I O N
0
M I N . F R E Q
1 5
H z
L E V E L ?
N O
P R E S S U R E
0 3 ,
0
b a r
T Y P E
S
I N G L E ?
P . S E N S O R
0 -
1 0
b a r
P s e t
4 ,
P b a r
3 ,
In case of group assembly, after pressing AUTOMATIC in the MASTER device, the AUTOMATIC LED LIGHT of the SLAVE device will
start to flash intermittently, indicating that communication between both devices is ready. If this does not happen verify the
connection (fig 5).
To start the sequence of configuration press MENU during 3"
0
9
By mean of keys pq we can choose the languages: "LANGUAGE ENGLISH", "LANGUE
FRANÇAISE", "LINGUA ITALIANA" and "IDIOMA ESPAÑOL".
By mean of keys pq input the nominal current intensity value in A of the pump
enabling the thermal protection. This value is located over the characteristics plate of
the motor. Press ENTER for validation.
WARNING: this value is linked with the flow detection system, it is very
important to enter the exact current consumption indicated on the
nameplate.
ROTATION SENSE. Using the START/STOP pushbutton verify the rotation sense. By
mean of keys pq(0/1) we can change it. Press ENTER for validation.
MINIMUM FREQUENCY. Using p we can increase the lower frequency value, within
15-48 Hz for 3-phase pumps and 30-48 Hz for single-phase pumps.
*The minimum frequency value will be used as frequency stop in installations where the
automatic detection of Speedbox do not act due to leaks in the system. See hydraulic
installation.
EXTERNAL LEVEL SENSOR. If the installation does not have level probe press
ENTER to validate NO.
If the installation has a level probe, use keys pqto change NO by Y.
This will be the system operating pressure. Use keys pq for modify the initial value (2
bar). WARNING ! The input pressure must be al least 1 bar lower than the
maximum pressure of the pumps.
NOTE: In case of group assembly, all the system operates at the pressure set in the
MASTER device, so that the configuration of set pressure in the slave device is superfluous.
The SPEEDBOX is configured by default as SINGLE.
In case of individual assembly just confirm SINGLE by pushing ENTER.
In case of group assembly (M-S), we will choose respectively SLAVE and MASTER in
each unit pushing q.
The range of lecture of the pressure transmitter installed must be adjusted.
If the range is within 0-10 bar confirm by mean of ENTER.
If the range is within 0-16 bar change it by mean of pq and then confirm with
ENTER.
After pressing ENTER pushbutton, the system is ready to operate. Press AUTOMATIC
0
in order to quit manual mode.
9
In case of group assembly press AUTOMATIC only in the device set as MASTER
-10-
MENU
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ON
START/
OFF
.

Publicité

loading