Wiring Information; Wiring Order; Commissioning Instructions - France Air ORDINYS Notice Technique

Coffret de relayage pour ventilateur de désenfumage
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.5 - WIRING INFORMATION

„4.5.1 Motor and power supply connection
Box type
PYROLYON cables
Designation
Fan motor
Fan motor
Fan motor
Fan motor
Fan motor
The cable cross-sections are given as an indication, it is possible to put a different section if the cable supports 1,5 x Nominal intensity
of motor.
For the motor connection, use a high temperature cable when it is in the airflow.

4.6 - WIRING ORDER

Please follow the steps below to ensure easy access and quicker connection:
1. Connect the box's entire power section (Proximity contacts and switches (on the version with the option)).
2. You can simulate smoke extraction by using the micro buttons located on the PCB.
3. Connect the control section to the PCB.
4. Connect the pressure switch, if present in the box.
5. Power on the relay box.
6. Perform a RESET for powering on.
A switch is installed in the box to connect the Pressure switch option version.

5. COMMISSIONING INSTRUCTIONS

If a safety order is issued when this button is pressed, this order will not be acknowledged
Location of terminals, keys, display on the PCB for 1-speed smoke extraction only box
For more information on the connections, please refer to the wiring diagram supplied with the box
NT 1920 C - 12/2019
Cross-section
4G2.5 mm²
4G4 mm²
4G6 mm²
4G10 mm²
4G16 mm²
When installing the box, press the RESET button located on the PCB to reset
the system and clear the faults.
and the safety order will need to be restarted.
3 A
8 A
12 A
18 A
X
X
X
X
25 A
X
8