THERMASREG
Mechanical temperature controllers ⁄ wet room temperature controllers THERMASREG
stainless steel capillary (spiral coil sensor), working without external voltage. They are used for monitoring and controlling temperatures in heat
generation plants, in heating, ventilation and air conditioning systems, for ventilation, cooling and climate control in halls, cold storage rooms,
greenhouses, nurseries, stables, breeding rooms, as industrial room thermostat or surface - mounted thermostat in industrial applications as well as
in wet room and outdoor areas.
TECHNICAL DATA
Switching capacity:
(Contact load)
Contact:
Housing:
Housing dimensions:
Cable gland:
Housing temperature:
Capillary:
Tolerance:
Electrical connection:
Routing:
Protection class:
Protection type:
Standards:
FUNCTION
®
THERMASREG
TR 040 ⁄ TR 060
Type ⁄ WG01
Temperature
Range
TR 040 ⁄ 060
T R - 0 4 0
0...+40 °C
T R - 0 6 0
0...+60 °C
TR 040 U ⁄ 060 U
T R - 0 4 0 U
0...+40 °C
T R - 0 6 0 U
0...+60 °C
TR 040 ⁄ TR 060
24...250 V AC +10 %, 16 A, cos ϕ = 1.0
24...250 V AC +10 %, 1.5 A, cos ϕ = 0.6
at 24 V AC min. 150 mA
dust-proof switch block unit as potential-free, single-pole or two-pole changeover contact
plastic, UV-resistant, material polyamide,
30 % glass-globe reinforced, 
colour traffic white (similar to RAL 9016)
108 x 70 x 73.5 mm (Thor 2)
M 20 x 1.5; including strain relief
–35...+65 °C
stainless steel V2A (1.4303)
T
± 3 K; T
± 3 K; at +20°C ± 1K
min
max
2
0.14 - 2.5 mm
via terminal screws
admissible vibration load ≤ ½g
I (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU,
low-voltage directive 2014 ⁄ 35 ⁄ EU
Heating: The preset setpoint (scale value) is equivalent to the switch-off value of the heating.
The switch-on value is lower by the amount of operating difference.
Contact 2 - 3 breaks when temperature rises to the preset value.
Cooling: The preset setpoint (scale value) is equivalent to the switch-on value of the cooling.
The switch-off value is lower by the amount of operating difference.
Contact 1 - 2 closes when temperature rises to the preset value.
Temperature controllers, one-step
Thermal Operating
Difference (fixed) approx.
2 K
2 K
2 K
2 K
®
TR 040 ⁄ TR 060 with switching output (one-step) and
Connecting diagram
Cooling
Heating
Max. Capillary
Item No.
Temperature
TR (External setting)
+65 °C
1102-1050- 1100- 200
+75 °C
1102- 1050- 1100-300
TW (Internal setting)
+65 °C
1102-1050- 2100- 200
+75 °C
1102-10 50-2100- 300
Rev. 2021 - V15