No: 24932 – 10/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMDI-100-U
BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go
adjustment is optional.
For full operational details, adjustment and more features of
the product, see the DLM System Installation Guide provided
with Wattstopper room controllers, and also available at
www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable
regulations, local and NEC codes. Wire connections shall
be rated suitable for the wire size (lead and building wiring)
employed.
For Class 2 DLM devices and device wiring: To be connected
to a Class 2 power source only. Do not reclassify and install as
Class 1, or Power and Lighting Wiring.
The LMDI-100 Serial Data Input/Output Device allows seamless integration of 3rd party devices
to the Wattstopper Digital Lighting Management Local Network (DLM) via RS-232 signaling and
defined protocol via RS-232 signaling and the Wattstopper defined protocol LMDI-100 Interface:
Host Commands reference document. Please reference the product resources section for the
LMDI-100 on www.legrand.us/wattstopper for the protocol commands list. The LMDI-100 connects
to the DLM local network and to 3rd party systems such as A/V. The LMDI-100 will respond to
strings as defined by the Wattstopper protocol.
Character strings sent from the commanding system associate with the appropriate DLM Local
Network action via the protocol defined in the LMDI-100 Interface: Host Commands reference
document, can activate DLM room functions and read status. Full-modem, electrically isolated
RS-232 signals are exposed individually via a 10 position, screw terminal connector.
Output Signals and LEDs
The LMDI-100 has red LEDs to indicate transmitted and received traffic, as well as power and DLM Local Network health. The
Configuration button allows the LMDI-100 to initiate Push-n-Learn
Signals exposed to the 3rd party system include RTS, CTS, TxD, RxD, and Gnd.
Installation shall be in accordance with all applicable regulations, wiring practices, and codes. Connect to a
Class 2 power source only.
• Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 1, 3 or Power and Lighting Wiring.
• Wire connections shall be rated suitable for the wire size (lead and building wiring) employed.
The LMDI-100 is UL2043 Plenum rated.
All connections to the LMDI-100 are Class 2 low voltage.
If code requires that the LMDI-100 be mounted in an enclosure, it can be mounted inside a 4" x 4" junction box,
inside a 2
/8" deep (or deeper) 2-gang wall box, in a 3" or 4" octagonal box, or on a din rail inside a panel.
1
Attach din rail clip.
Wattstopper
DLM - Serial Data Input/Output Device
Gestion numérique de l'éclairage - Dispositif d'entrée/de sortie de données série
Control de la iluminación digital - Dispositivo de entrada/salida de datos en serie
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
operation,
DESCRIPTION AND OPERATION
MOUNTING AND WIRING
Option 1:
Option 2:
Attach to din rail.
Mount to wall.
®
Voltage ................................................................... 24VDC
Current Consumption ............................................... 15mA
Power Supply .................... Wattstopper Room Controllers
Connection to DLM Local Network ............... 2 RJ-45 ports
Electrical Isolation ratings ........................................ 1500V
Environment ...................................... For Indoor Use Only
Operating Temperature ......32° to 104°F (0° to 40°C)
Storage Temperature ....... 23° to 176°F (-5° to 80°C)
Relative Humidity ........... 5 to 95% (non condensing)
Other:
RoHS compliant, UL2043 Plenum rated.
Patent Pending
programming mode as with other DLM Local Network products.
TM
Inside a 2-gang J-Box
SPECIFICATIONS
RJ45 ports (2)
Configuration LED
Configuration
push button
LEDs (2)
Connect to
DLM local network
NOT Ethernet
RX
TX
RTS
CTS
Green LEDs
Not Used
Not Used
RS-232 Tx
RS-232 Rx
Not Used
GND

Publicité

loading

Sommaire des Matières pour LEGRAND Wattstopper LMDI-100-U

  • Page 1 Host Commands reference document. Please reference the product resources section for the RJ45 ports (2) LMDI-100 on www.legrand.us/wattstopper for the protocol commands list. The LMDI-100 connects Configuration LED to the DLM local network and to 3rd party systems such as A/V. The LMDI-100 will respond to...
  • Page 2 MOUNTING AND WIRING Attach the LMRJ Cable The DLM local network uses free topology low voltage wiring. The LMDI-100 can connect anywhere on the DLM local network. Line Voltage Switch Loads Room Controller LMRJ Cables CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE RS-232 Data Wiring Input/Output to Third Party...
  • Page 3 ..............Contrôleur de pièce DLM fourni avec Wattstopper contrôleurs de pièce et aussi disponible au Alimentation électrique ............. Wattstopper www.legrand.us/wattstopper. Branchement sur le réseau DLM local ......2 ports RJ-45 Valeurs nominales d’isolation électrique ......... 1 500 V L'installation doit être effectuée conformément à tous les règlements ..............
  • Page 4 MONTAGE ET CÂBLAGE L’installation doit être conforme à toutes réglementations, les pratiques de câblage et les normes applicables. Raccordez l’appareil à une source d’alimentation de classe 2 uniquement. • Câblage pour dispositif de classe 2 uniquement - Ne le reclassez pas et n’installez pas de câblage de classe 1, 3 ou d’alimentation et d’éclairage.
  • Page 5 RACCORDEMENT DES BORNES Avec contrôle de débit Avec contrôle de débit Aucun contrôle de débit RACCORDEMENT RACCORDEMENT RACCORDEMENT DU LMDI-100 DU DISPOSITIF DTE DU DISPOSITIF LMDI-100 DISPOSITIF DCE LMDI-100 RxD Borne 1 RxD Borne 1 RxD Borne 1 TxD Borne 2 TxD Borne 2 TxD Borne 2 RTS Borne 4...
  • Page 6 Fuente de alimentación ......... habitación Wattstopper proporciona con los controladores de habitación Wattstopper; también Conexión a la red local de DLM ..........2 puertos RJ-45 está disponible en www.legrand.us/wattstopper. Aislamiento eléctrico nominal ..............1500 Vt Entorno ..............Solo para uso en interiores La instalación debe realizarse conforme con todas las...
  • Page 7 Conecte el cable LMRJ La red local de DLM usa cableado de bajo voltaje detopología libre. La unidad LMDI-100 se puede conectar en cualquier lugar de la red local de DLM. Voltaje de línea Interruptor Controlador de habitación Cargas Cables LMRJ PRECAUCIÓN: PARA CONECTAR UNA COMPUTADORA A LA RED LOCAL DE Cableado de datos RS-232...
  • Page 8 No. 24932 – 10/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.