Electrical Installation; Wall Controller; Upper Temperature Sensor - Bigassfans Powerfoil X2.0 Manuel D'installation

Smartsense
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

WARNING: Disconnect fan and controller from power supply before installing the SmartSense.
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician!
Incorrect assembly can cause electric shock or damage the motor and the controller! Hazard of electrical
shock!
WARNING: Installation must be in accordance with the National Electrical Code, ANSI/NFPA 70-2011,
and all local codes. The procedures and techniques outlined in this manual are merely a guide for proper
installation. Code compliance is your responsibility! Failure to comply with these codes could result in
personal injury or property damage.
WARNING: The fan controllers contain high voltage capacitors which take time to discharge after removal
of mains supply. Before working on the fan controller, ensure isolation of mains supply from line inputs
at the fan controller's disconnect (L1, L2/N, L3). Wait three minutes for capacitors to discharge to safe
voltage levels. Failure to do so may result in personal injury or death. Note: Darkened display LEDs are
not an indication of safe voltage levels.

Wall controller

Supply voltage
Power consumption
Output
Wiring
Max wiring distance (ft)
Operating temperature
Humidity
Storage temperature
ESD withstand voltage

Upper temperature sensor

Supply voltage
Power consumption
Output
Accuracy
Non-linearity
Wiring
Operating temperature
Humidity
Storage temperature
ESD withstand voltage

ELECTRICAL INSTALLATION

+24 VDC, 100 mA
≤ 1 W
4–20 mA DC current loop
18–22 AWG
((Vsupply-10 V)/0.02 A) / (Wire Ohms per Foot x 2)
32° to 100° F (0° to 38° C)
95% Relative humidity. Board is conformal coated
14° to 122° F (-10° to 50° C)
+/- 4 kV Air, +/- 4 kV Contact
+10 VDC to +24 VDC
≤ 1 W
4–20 mA DC current loop
+/- 1° @ 77° F (+/- 0.5° @ 25° C)
+/- 0.5° F
18–22 AWG
32° to 100° F (0° to 38° C)
95% Relative humidity. Board is conformal coated.
14° to 122° F (-10° to 50° C)
+/- 4 kV Air, +/- 4 kV Contact
WWW.BIGASSSOLUTIONS.COM
© 2015 DELTA T CORP.
ALL RIGHTS RESERVED.
11