Maintenance and repairs

Suitable maintenance is crucial for obtaining longer life, perfect working conditions and high
efficiency of the unit as well as for ensuring the safety features provided by the
manufacturer.
12

Routine maintenance

Good operation of the unit requires the condenser to be cleaned periodically (frequency of
cleaning depends on the environment where the unit is installed).
Turn off the unit and clean it by blowing air from the inside outwards. Should no air jet be
available, use a long-haired brush and work on the outside of the condenser.
In case of water-cooled condensers have the unit cleaned by a plumber with special
descaling agents.
W AR NI NG
Use safety gloves to protect your hands from possible cuts.
W AR NI NG
Disconnect the unit before w orking on it.

12.1 Periodical maintenance

Periodically check wear condition of electrical contacts and remote switches; if necessary
replace them.

12.2 Service operations to be carried out by qualified technicians or by the manufacturer

Following operations shall be carried out by qualified technicians or by the manufacturer
exclusively. Under no circumstances the user is allowed to:

12.3 Troubleshooting

During operation following troubles may occur:
1 Compressor stops. The unit is equipped with an overtemperature device which stops the
compressor every time the max. allowable temperature of motor windings is exceeded.
Possible causes are:
2
32
replace electrical components
work on the electric equipment
repair mechanical parts
work on the refrigerating system
work on the control panel, ON/OFF and emergency switches
work on protection and safety devices.
- insufficient ventilation of the room where the unit is installed;
- anomaly in mains voltage;
- faulty operation of condenser fan.
Device reset is automatic.
Ice forms on the evaporator preventing air from flowing regularly.
Possible causes are:
- the door is opened too frequently;
- faulty operation of evaporator fan;
- faulty solenoid valve (in models with hot gas defrost);