7.7 Anti-legionnaire's disease protection (function activated only through the installer menu)

If activated, the water heater automatically carries out the anti-legionnaire's disease protection function. The water is
brought to a temperature of 65°C on a monthly basis and for a maximum time of 15 minutes, so as to avoid germs
from developing in the water tank and piping (provided the water has not been brought to T>57°C at least once for at
least 15 minutes). The first heating cycle is performed 3 days after the function has been activated. As these
temperatures may cause burns, it is advisable to use a thermostatic mixer.
Code entering to access the installer menu. The number 222 appears on the display: turn the
knob until reaching number 234 then press the knob. It will then be possible to access the
installer menu.
Adjustment of the maximum obtainable temperature (from 65°C to 75°C).
A higher temperature value allows for using a greater amount of hot water.
Adjustment of the minimum obtainable temperature (from 50°C to 40°C).
A lower temperature setting allows for more energy-efficient operation in the event of limited
hot water consumption.
Adjustment of the maximum temperature obtainable with the heat pump unit (from 50°C to
62°C). Bear in mind that operating at temperatures above 55°C with the heat pump may lead
to greater wear of the compressor.
Activation/deactivation of the Green function (on/off).
See Paragraph 7.4.
Activation/deactivation of the Anti-Legionnaire's Disease function (on/off).
See Paragraph 7.7.
Activation/deactivation of the Voyage function (on/off).
See Paragraph 7.4.
Activation/deactivation of the defrost mode (on/off).
If activated, this mode allows the heat pump to function at air temperatures as low as -5°C.
Activation/deactivation of the two-tier rate operation mode.
See Paragraph 7.9.
Maximum number of hours of daily heating (from 5h to 24h).
Resetting of all factory default settings, remember to reset P7 to ON.