12. AQUATIMER A3000 open – Variant 1
Connection example for electrical installation
Electrical T-junction in the ceiling area
Materials required
To be provided by the customer:
• Damp-room junction box (≥100 mm × ≥100 mm)
• Earth leakage circuit breaker (RCD)
• Conduit for electronic-module extension line (Ø 16 mm)
• Conduit for system line
Accessories
A3000 open ECC function controller
with Ethernet connection . . . . . . 4893 00 00
System line
blue, 100 m . . . . . . . . . . . . . . . . 84-032-12.468
blue, 25 m . . . . . . . . . . . . . . . . . 84-032-12.534
gray, not halogen-free, 100 m . . 84-032-12.563
gray, not halogen-free, 25 m . . . 84-032-12.720
Extension line
for electronic module . . . . . . . . . 84-032-12.399
Terminating resistor . . . . . . . . . . . 84-100-17.143
Preparing the electrical connection
Position the power supply outside of the wet area, in a separate room, and protect it
with an earth leakage circuit breaker (RCD).

Important!

Only use original lines.
12.1 Install one damp-room junction box (a) for each in-wall installation box (a).
12.2 Install a conduit (c, Ø 16 mm) from the damp-room junction box to the in-wall instal-
lation box.
12.3 Lay the system line (b) through the conduit and loop it from the damp-room junction
box to the damp-room junction box.
12.4 Connect the electric T-junction (d).
12.5 Slide the extension line (e) for the electronic module through the conduit (c).
12.6 Plug the extension line (e) for the electronic module on the electric T-junction (d).
12.7 Close up the damp-room junction box with the protective cap (f).