11. AQUALINE-Therm with Thermal Disinfection

Connection example for electrical installation
Materials required
To be provided by the customer:
• Damp-room junction box (≥100 mm × ≥100 mm)
• Earth leakage circuit breaker (RCD)
• Conduit for connection pipe bypass solenoid-valve (Ø 16 mm)
• Conduit for electric line
• Flexible 2-core electric line (type H05VV-F 2×0.75 mm²)

Accessories

Power supply (230 V AC/24 V DC)
System power supply . . . . . . . . 4841 10 00
Key switch . . . . . . . . . . . . . . . . . . 4850 10 00
Connection line
for bypass solenoid-valve . . . . . 84-032-12.520
Preparing the electrical connection
Position the power supply and the key switch outside of the wet area, in a separate
room, and protect them with an earth leakage circuit breaker (RCD).
11.1 Install one damp-room junction box (a) for each fitting.
11.2 Install a conduit (c; Ø 16 mm) from the damp-room junction box to the in-wall instal-
lation box.
11.3 Lay a flexible 2-core electric line (b) through the conduit and loop it from the damp-
room junction box to the damp-room junction box.
11.4 Slide the connection line (d) for the bypass solenoid-valve through the conduit (c).
The plug must be easily accessible within the in-wall installation box.
11.5 Connect the connection line (d) for the bypass solenoid-valve to the damp-room
junction box.
11.6 Close up the damp-room junction box with the protective cap (e).
Order No.
7