TESTING
MAN mode: add one step, the power factor (cos ϕ) should improve
indicated by a value which is bigger in the inductive range as before.
AUTO mode: after setting the target cos ϕ, RVC should reach this
value after having switched steps.

TECHNICAL SPECIFICATIONS

Measuring system:
Micro-processor system for
balanced three-phase networks
or single-phase networks.
Operating voltage:
100V to 440V.
Voltage tolerance:
+/- 10% on indicated operating
voltages.
Frequency range:
50 or 60 Hz +/- 5% (automatic
adjustments to network
frequency).
Measuring circuit terminals
(L2, L3 and k, l):
CAT. III rated.
Current input:
1A or 5A (RMS).
Current input impedance:
<0.1 Ohm (recommended CT
class 1.0, 10 VA min).
Consumption of the
controller:
8 VA max.
Output contact rating:
• Max. continuous current: 1.5A.
• Max. peak current: 5A.
• Max. voltage: 440 Vac.
• Terminal A is rated for a
continuous current of 16A.
Alarm contact:
• Normally open contact.
• Max. continuous current: 5A.
• Rated/max. breaking voltage:
250Vac/440Vac.
Power factor setting:
From 0.7 inductive to 0.7
capacitive.
Starting current setting (C/k):
• 0.01 to 3A .
• automatic measurement of C/k.
Number of outputs:
RVC 3: 3
RVC 6: 6
RVC 8: 8
Switching time between steps:
programmable from 1s to 999s
(independent of reactive load).
Switching sequences:
User defined.
12
RVC 10: 10
RVC 12: 12