Technical Information
How to Connect the Open-Collector Inputs of the Controller
Tab. 6
Data type
Logic (L)
Numeric (N)
Alphanumeric (A)
The addressed SLAVE will respond with an ANSWER whose structure depends
from the MESSAGE type.
When the MESSAGE is a reading command, the SLAVE will respond
transmitting a string with the same structure of the MESSAGE.
Using the RS 485 interface, the message structure remains identical to the one
NOTE
used for the RS 232 interface, the only difference being that the value assigned
to the ADDRESS <ADDR>
The controller can answers with the following response types:
288/328
<ADDR> (Unit address) = 0x80 (for RS 232)
<ADDR> (Unit address) = 0x80 + device number (0 to 31) (for RS 485)
<WIN> (Window) = a string of 3 numeric character indicating the window
number (from '000' to '999'); for the meaning of each window see the
relevant paragraph.
<COM> (Command) = 0x30 to read the window, 0x31 to write into the
window
<DATA> = an alphanumeric ASCII string with the data to be written into
the window. In case of a reading command this field is not present. The
field length is variable according to the data type as per the following
table:
Field length
1
6
10
<ETX> (End of transmission) = 0x03
<CRC> = XOR of all characters subsequent to <STX> and including the
<ETX> terminator. The value is hexadecimal coded and indicated by two
ASCII character.
TV 551/701 Navigator User Manual / 87-900-934-01 (P)
Valid characters
'0' = off
'1' = on
'-', '.', '0' . . . '9' right
justified with '0'
from blank to '_' (ASCII)