DC voltage only
1
:
12...33 V
(possible with standard version,
non-Ex, without electric isolation)
12...30 V
(necessary with Ex version, type
of protection "Intrinsic safety"
Ex ia IIC T6, without electric
isolation)
Max. residual ripple:
10% p.p.
Max. current
consumption:
Approx. 5 mA + I
Mechanical withstand
Permissible vibration
(without additional
gear):
5 g every 2 h in 3 directions
f ≤ 200 Hz
Shock:
3 ×50 g
10 shocks each in 3 directions
Permissible static load
on the shaft:
Sense
radial max. 16 N
axial max.
If subjected to vibration the shaft
load should be as low as possible to
ensure optimum life of the bearing
Mounting position:
Any
Material
Housing:
Cast aluminium
Corrosion resistant fi nish
Plastic protection cap
Cable glands:
Metal
Regulations
Electromagnetic
compatibility:
The standards EN 50 081-2 and
EN 50 082-2 are observed
Intrinsic safety:
Acc. to EN 60 079-11: 2007
Test voltage:
2,2 kVeff, 50 Hz, 1 min.
between...
... power supply and housing
... power supply and measuring
(with DC, AC power supply, with
electric isolation)
500 Veff, 50 Hz, 1 min.
all electrical connections to
housing
(with DC power supply, without
electric isolation)
Housing protection:
IP 43 acc. to EN 60 529
without gear
IP 64 with gear or other similar

mounting

Impulse voltage
withstand:
1 kV, 1,2/50 μs, 0.5 Ws
IEC 255-4, Cl. II
Permissible common-
mode voltage:
100 V, 50 Hz
A
Drive shafts dia.
2 mm
6 mm resp.
1/4ʺ
83 N
25 N
130 N
output
Environmental conditions
Climatic rating:
Standard version
Temperature – 25 to + 70 °C
Annual mean relative humidity
≤ 90% or
version with improved climatic ra-
ting
Temperature – 40 to + 70 °C
Annual mean relative humidity
≤ 95%
Ex version
Temperature – 40 to + 60 °C at T6
resp. – 40 to + 75 °C at T5
Transportation and
storage temperature:
– 40 to 80 °C
6. Mounting
The relationship between the types of mounting, or more
precisely the corresponding cut-out diagrams and the different
versions of the transmitter can be seen from Table 2.
Table 2:
Transmitter
versions
Continuation of table 2 see on next page!
1
Polarity reversal protection. The voltage must not fall below 12 V.
Drilling and cut-out diagrams
for mounting transmitters ...
3.2
5
M3
M4
19