Helios AIR1-EVH RH Série Notice De Montage Et D'entretien page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
NOTE
Electrical pre-heater AIR1-EVH RH
A: Minimum distance for servicing the electrical pre-heater.
The electrical pre-heater can be used in both air flow directions. Determine the service side and align the pre-heater
accordingly before assembly.
1. Apply sealing strips where the module joins the unit (see Fig. 3).
2. Remove screw covers on the unit before installing the module (see Fig. 4).
3. Connect the temperature sensor (included in delivery) to the outdoor side of the pre-heater. Fasten the sensor cable
to the sheet metal part with a cable tie (see Fig. 5).
Fig .3
Fig .4
5
Fig .2
Type
A (mm)
AIR1-EVH RH 1500
960
1060
AIR1-EVH RH 2000
AIR1-EVH RH 3000
1170
AIR1-EVH RH 5000
1440
AIR1-EVH RH 6000
1560
AIR1-EVH RH 8000
1810
AIR1-EVH RH 9500
1910
AIR1-EVH RH 12000
2060
AIR1-EVH RH 15000
2310
Fig .5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Air1-evh rh 1500Air1-evh rh 2000Air1-evh rh 3000Air1-evh rh 5000Air1-evh rh 6000Air1-evh rh 8000 ... Afficher tout

Table des Matières