Leds Of The Controller; Test Mode - Fermax 4420 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

LEDs of the controller

For each reader, the DC can control two LEDs (red and green) and one buzzer (sound alerts
generated by the readers). Depending on the combination of functions of these three ele-
ments, the status of the Door can be known at any time. The possible statuses indicated are:
Status
Door closed (standby)
Door-opener active
Door unblocked
Door blocked
Door forced/left open
Request for PIN code
Without power

Test Mode

This mode lets you check the correct operation of the DC and the elements connected to it at
any time (readers, Trades and Exit button, open door relay, door sensor and auxiliary relay).
Connection to the central is not necessary to carry out this type of test, so you can check the
installation before it is completed.
1º. To enter test mode, press the door controller TEST button. The readers connected
to the DC give off 3 discontinuous beeps, signalling that it is in test mode.
2º. Checking:
In test mode, when any card is presented, introducing any keypad code, pressing
the exit or Trades button, the door release relay is activated for 5 seconds.
If the door is opened or if any changes are registered in the door sensor, the auxiliary
relay is activated for 5 seconds.
The LEDs and Buzzers (acoustic alerts generated by the readers) must operate in
their normal code.
Notes:
The access control central unit does not intervene during the test.
If you press the TEST button while in TEST mode, the DC readers emit a continuous sound, indicating
that you are exiting test mode.
After 2 minutes without any actions taking place, it goes back into normal mode.