3. Installation notes
Assembly/installation should only be carried out by
qualified person exercising due care.
Switch off the heating system before assembly.
Check and make sure that the connection wires
are not live.
Assembly note:
– only use PVC-sheathed cables (solid wire)
during installation
– may only be attached to a non-conducting,
level and stable surface
– only suitable for ambient conditions where
normal quantities of dirt occur
– if installed properly in accordance with
VDE 0100, Part 40, the components where
contact remains possible may be regarded
as doubly insulated (Class of protection II)
Operating note:
This unit's electronic unit has been protected
from external interference. However – depending
on the type of assembly – remember that the
mains voltage may be overlaid with extremely
high interference voltage peaks. Also, when
switching coils, e. g. solenoid valves, contactors,
interference occurs that may affect an electronic
unit in spite of all internal protective measures.
To guarantee the greatest operating safety, the
following details must be observed when
connecting:
– where larger plants are concerned, it will
be necessary to shield coils, e. g. solenoid
valves, contactors, that are switched directly
by the unit with a suitable varistor or
RC element
– if inductive DC voltage consumers are
switched, a free-wheeling diode must be
added
– inductive and capacitive loads especially
exert a lot of stress on the output contacts.
In individual cases check, whether the installation
requires
– an isolation relay or contactor or
– an interference suppression filter, e. g. Type
NEF 2.-1,0 A, Messrs. Murr.