Télécharger Imprimer la page

Before Installation - Toshiba TCS-NET Manuel D'installation

Gsm phone control interface

Publicité

Les langues disponibles
  • FR

Les langues disponibles

TCS-NET GSM Phone Control Interface
3

Before Installation

Specifications
Media used
Operation
Air conditioner control items Air conditioner ON/OFF control is designated by mobile phone SMS message.
Air conditioner status
acquisition items
Operation/notification target
telephone number
Accessible telephone
number
TCB-IFGSM1E
Power supply
hardware
Power consumption
RS-232C connector
Connector for the air
conditioner
Operating temperature/
humidity
Storage temperature
Chassis material
Dimensions
Mass
No.
Line
1
RS-232C cable
2
Indoor unit cable
3
Power
(*1) Thickness of insulator must be at least 1 mm. When the insulator is thinner than 1 mm, put the wire into a vinyl
tube with insulator thicker than 1 mm.
(*2) Varies with use environment and conditions.
An AC adaptor unit required when connecting to the HA connector CN08/CN09/CN22 must be procured locally.
The AC adaptor must meet the following requirements.
Global System for Mobile Communications (2G digital mobile phone
communication system)
Air conditioner ON, OFF, and alarm status is notified by mobile phone SMS
message. (Auto-notification is provided only when CN61 is used.)
Up to 5 numbers can be registered initially.
Up to 5 numbers can be registered initially.
Specified by AC adapter
No external power supply is required when CN61 is used.
1.1 W
Supports communication specifications (9600bps, non-parity, 8 bits, 1 stop bit,
flow control provided/none)
D-sub 9-pin male connector
Protocol: Supports ETSI GSM 07.05, GSM 07.07, GSM 03.40, GSM 03.38
standard compliant SMS-related AT commands.
Photocoupler HA connector specification, 12 VDC power input, alarm input
CN3: HA connector (For CN08/CN09/CN22)
CN4: For CN61
0 to 40°C, 20 to 85% RH
-10 to 60°C
Plastic (nonflammable ABS resin UL-94V0)
32 (H) × 80 (W) × 125 (D) mm
150 g
Description
Type
Straight-type cable with D-sub 9-pin male-female connectors
Wire size
Conforming to RS-232C
Length
Max. 15 m
Type
Multi-core wire
Wire size
Stranded wire (*1) 0.08097 to 3.309 mm² (AWG28 to AWG12)
Length
Max. 2 m (*2)
Specified by AC Adapter
Not required when CN61 is used
– 7 –
Installation Manual
EN
6-EN

Publicité

loading

Ce manuel est également adapté pour:

Tcb-ifgsm1e