Setting The Calibration Temperature T - GF JRGUTHERM 2T Notice De Montage Et D'utilisation

Régulateur de circulation thermostatique avec robinetterie d'arrêt
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.3 Setting the calibration temperature T

(disinfection)
The desired calibration temperature T
be taken from the table. The values given are
reference values covering the desired thermal
disinfection temperature control range of
70-75°C.
1
3
Settings for thermal disinfection
1 Scale ring (gradation: 0-5)
2 Allen key SW4
3 Hexagon socket
Remove the sealing cap, apply Allen key (2)
to the hexagon socket (3) and set the desired
scale value.
Warning
2
Don't exceed the stop (minimum/
can
maximum) when adjusting the
2
temperature.
Setting the disinfection temperature
simultaneously sets the starting temperature
(switching point) of the disinfection.
Example
A change in the scale setting from 0 to 3
2
corresponds to an increase in the disinfection
temperature of 70°C to 73°C.
Simultaneously, the starting temperature
of the disinfection is increased by 3K to 69°C.
E
85