WIKA A-10 Mode D'emploi page 20

Masquer les pouces Voir aussi pour A-10:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Commissioning, operation
Fitting a DIN 175301-803 angular connector
GB
(D) Mounting hole
1. Loosen the screw (1).
2. Loosen the cable gland (2).
3. Pull the angle housing (5), with the terminal block (6)
inside, away from the instrument.
4. Via the mounting hole (D), lever the terminal block (6)
out of the angle housing (5). Do not try to push the
terminal block (6) out using the screw hole (1) or the
cable gland (2), otherwise the sealing of the angle
housing could be damaged.
5. Select a conductor with an outer diameter matched to the angle housing's cable gland. Slide the
cable through the cable gland (2), washer (3), gland seal (4) and angle housing (5).
6. Connect the cable ends to the appropriate connection terminals on the terminal block (6) (see table
"Electrical connections").
7. Press the angle housing (5) onto the terminal block (6).
8. Tighten the cable gland (2) around the cable. Make sure that the seals are not damaged and that
the cable gland and seals are assembled correctly in order to ensure ingress protection.
9. Place the flat, square gasket over the pressure transmitter's connection pins.
10. Slide the terminal block (6) onto the pressure transmitter's connection pins.
11. Secure the angle housing (5) and terminal block (6) to the pressure transmitter with the screw (1).
20
WIKA operating instructions pressure transmitter model A-10
(1)
(2)
(3)
(5)
(4)
(6)
Line connector
(female)
Sealing
Instrument connector
(male), case with
process connection

Publicité

Table des Matières
loading

Table des Matières