21. Installation in the USA and Canada
In order to maintain the cETLus approval,

Nota

follow these additional installation instructions.
The ETL approval is according to UL 1004-1.
21.1 Electrical codes
This product complies with the Canadian Electrical Code and
the US National Electrical Code.
This product has been tested according to the national standards
for Electronically Protected Motors:
CSA 22.2 100.04: 2009 (applies to Canada only).
UL 1004-1: June 2011 (applies to USA only).
Codes de l'électricité
Ce produit est conforme au Code canadien de l'électricité et
au Code national de l'électricité américain.
Ce produit a été testé selon les normes nationales s'appliquant
aux moteurs protégés électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada uniquement).
UL 1004-1: Juin 2011 (s'applique aux États-Unis uniquement).
21.1.1 Radio communication
This device complies with part 15 of the FCC rules and RSS210
of IC rules.
Operation is subject to the following two conditions:
This device may not cause interference.
This device must accept any interference, including interfe-
rence that may cause undesired operation of the device.
21.1.2 Identification numbers
For USA
Grundfos Holding A/S
Contains FCC ID: OG3-RADIOM01-2G4.
Pour le Canada
Grundfos Holding A/S
Modèle: RADIOMODULE 2G4
Contient IC: 10447A-RA2G4M01.

21.2 Electrical connection

21.2.1 Conductors
Use 140/167 °F (60/75 °C) copper conductors only.
21.2.2 Torques
Maximum tightening torques for the terminals can be found in
section Torques, page 37.
21.2.3 Line reactors
Maximum line reactor size must not exceed 1.5 mH.
21.2.4 Fuse size/circuit breaker
If a short-circuit occurs, the pump can be used on a mains supply
delivering not more than 5000 RMS symmetrical amperes, 600 V
maximum.
Motor size
Fuse size
0.25 to 2.2 kW
25 A
Fuses
When the motor is protected by fuses, they must be rated for
480 V. Maximum sizes are stated in the table above.
Motors up to and including 2.2 kW require class K5 UR fuses.
Circuit breaker
When the pump is protected by a circuit breaker, this must be
rated for a maximum voltage of 480 V. The circuit breaker must
be of the "inverse time" type.
The interrupting rating (RMS symmetrical amperes) must not be
less than the values stated in the table above.
21.2.5 Overload protection
Degree of overload protection provided internally by the drive,
in percent of full-load current: 102 %.
Nous nous réservons tout droit de modifications.
1
Circuit breaker type/model
25 A / inverse time
37