User Input 2, Airflow Device, LWD
Microface 1
C
Open : UI active
Closed : UI inactive
in case of LSI:
Open : Cylinder empty
Closed : Cylinder full
NOTES : ALWAYS USE RELAYS TO CONNECT EXTERNAL CONTACTS TO THE Microface!
NEVER CONNECT EXTERNAL COMMANDS DIRECTLY TO THE Microface!
Airflow Sensor or Differential Pressostat (Contact) for Fans supervision are
alternative.
Warning, Alarm and Fan Output
Microface 1
DIG Out 0
Dehumidification
(max.24VAC)
NOTE 1 :
Dehum. Output can be programmed as :Dehumidification, Warning,
No Power message or not used. (all Functions are alternative)
72
FRANCAIS
ANA IN 0
PTC 6
(Jumper not set)
6
GND
Open : OK
Closed : Fan
Failure
All except FC = Air
DIG Out 7
G
Alarm
(max.24VAC)
Manuel d'utilisation Microface E & Hiromatic G/E rév.12.06.2002
alternative
ANA IN 0
(Jumper set)
0
G
G0
0
Airflow Sensor
DIG Out 8
S
8
G0
Fan Output
ANA IN 2 (Jumper not set)
Gnd
2
Leakage Water Detector
FC = Air only
DIG Out 2
G
2
Fan Contactor
72