Electrical Heaters Control: all units except 1 Compressor + FC Glyc
Microface 1
DIG Out 3
DIG Out 4
3
PC1
Heater 1
Heater 2
NOTE :
Electrical Heaters Control: Units with 1 Compressor + FC Glyc
Microface 1
ANA Out 0 or 1 (selectable)
G0
G
0 or 1
NOTE : If the Alarm Board is set
as Heater Board (as indicated),
on C2-R2 there is LWD Alarm,
on C3-R4 there is Fan Failure,
on C3-R5 there is Compressor Fail
additionally (normally open Contacts).
71
FRANCAIS
Heaters Alarm Input
4
G
PC1
Safety
Thermostat
PC2
G
C2
R2
C3
R4
R5
Heater 1
Manuel d'utilisation Microface E & Hiromatic G/E rév.12.06.2002
PTC 5
ANA IN 1 (Jumper not set)
5
C
PC2
Open : Alarm
PC1
Closed : OK
FC Air only
ANA IN 1 (Jumper not set)
G0
PC1
Safety
Thermostat
PC2
PC1
Heater 2
Heaters Alarm Input
1
Gnd
PC2
Open : Alarm
Closed : OK
Heaters Alarm Input
1
Gnd
PC2
Open : Alarm
Closed : OK
Contact from
Fan Contactor