Table Of Overload Times - Riello 5000VA Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

T
ABLE OF OVERLOAD TIMES
OVERLOAD TIMES
100% < Load ≤ 125%
125% < Load ≤ 150%
Load > 150%
OPERATION FROM
BYPASS
Activates bypass after 2 sec
Shutdown after 120 sec
Activates bypass after 2 sec
Shutdown after 4 sec
Activates bypass instantaneously
Shutdown after 1 sec
T
ECHNICAL DATA TABLE
INVERTER
Shutdown after 60 sec
Shutdown after 4 sec
Shutdown after 0.5 sec
65

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

6000va6500va8000va10000va

Table des Matières