Compliance with the description of the configuration softwar e,
the operating instructions of the AS-i safety monitor and the
operating instructions of the AS-i safety module ar e mandato-
ry!
Maintenance requirement
A minimum of one testing per year is compulsory by a demand
on the safety function.

Installation / electrical connection

Connect the AS-i safety pcb to two mechanical (positively driven) nc
contacts. In doing so, the two outer mechanical pins are connected to
one side of the nc contacts. The other side of the nc contacts is con-
nected with the two black cables.
The AS-i safety pcb must be installed in a protected location (e.g. con-
trol cabinet, housing). The appropriate housing must have a protection
rating of at least IP54. The unused open strands must be insulated. A
set-up test must be carried out after installation of the AS-i safety pcb.
When installing the AS-i safety pcb, cr o ss faults between the pins
of the mechanical contacts must be avoided. The connecting
strands of the AS-i safety pcb must not be made longer .