R E AD A N D S AVE THE S E I NS TRU C T I O N S
WARNING — TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE
THE FOLLOWING :
A - Your dryer installation incorporates a dryer exhaust power ventilator (DEDPV)
incorporating a lint trap.
B - Your dryer depends on the DEDPV for its safe and efficient operation. Operating your
dryer without a functional DEDPV will result in inefficient dryer operation, excess energy
consumption and a possible fire hazard. See warning light on DEDPV front panel.
C - The DEDPV shall be permanently installed within the space in which the dryer
is installed. In the case of a dryer installed in an alcove provided with a door, the DEDPV
shall be installed within the alcove or be installed immediately adjacent to the doors of the
alcove. The DEDPV shall be located where it will be readily visible after the dryer is installed
without opening any doors other than those necessary to access the dryer.
WARNING — IF A CONTINUOUS ALARM SOUNDS OR A VISUAL ERROR INDICATOR IS PRESENT,
DO NOT OPERATE THE CLOTHES DRYER. CONTACT YOUR SERVICE PERSONNEL
• Do not install in an exhaust ductwork of a clothes dryer whose instructions prohibit the
installation of a clothes dryer booster fan (DEDPV).
• Do not install in an exhaust ductwork where the equivalent duct length is less than 25 ft
(7.62 linear metres).
• The VTX-DEDPV is suitable to overcome an equivalent duct length of 130 feet
(39.6 meters) of 4 inch diameter galvanized steel duct, and to maintain an air velocity
of 1200 fpm (6.10 m/s).
• Do not exhaust air in excess of 167F (75C) and do not install less than linear 4ft (1.21m)
from clothes dryer exhaust outlet.
• Do not install less than 4 linear feet (1.21 linear meters) or more than 45 linear feet (13.71
linear meters) from clothes dryer exhaust outlet.
• Insulated dryer duct shall not be used upstream of the ventilator.
• The ventilator must not be used in conjunction with high output dryers.
• For general ventilating use only. Do not use to exhaust hazardous or explosive materials
and vapors.
• The installation must comply with local electrical and mechanical building codes,
and must be inspected and accepted by local authorities having jurisdiction.
INSTALLATION GUIDELINES
TO PREVENT THE POSSIBILITY OF DRYER FAN CAVITATION AND/OR EXHAUSTING EXCESS
HEAT REQUIRED FOR THE DRYING CYCLE AND COMPROMISING DRYING TIMES, BOOSTER FAN
AIRFLOW MUST NOT EXCEED THE DRYER FAN CAPACITY.