5.3.3 TIMER SETTING
The timer has two ways of operation:
To turn off
(When power on)
To turn on
(When power off)
Cancel timer
5.3.4 Automatic Defrost
At low room temperatures, frost may buildup at the evaporator during
operation. The unit will automatically start defrosting and the POWER LED
blinking. The defrost control sequence is as follows:
A. When the unit operates in the cooling operation, drying operation, the
ambient temperature sensor senses the evaporator coil temperature is
below -1°C, after the compressor will stop operating for 10 minutes or
the coil temperature up to 7℃, the unit restart to cool operating mode.
B. When the unit operates in the heating operation, drying operation,
once the coil temperature sensor senses the temperature of the
evaporator is below 40℃ and the differential temperature between coil
temperature and room temperature is below 19℃ after the compressor
operation for 20minutes, the unit start defrosting for 5 minutes and the
power indicator blinking.
(1hour-24hours):
Press Timer key to
turn on the timer
function.
Press Timer key to
turn on the timer
function.
Press Up /Down repeatedly until the LED shows '00'.
Note: when press POWER will also exit the timer setting.
Press Up /Down
repeatedly to set the
delay OFF time.
Press Up /Down
repeatedly to set the
delay ON time.
93