a Before obtaining access to terminals, all power supply circuits must be interrupted.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR OPTIONAL EQUIPMENT COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRQUIT, LEAKS, FIRE OR OTHER DAMAGE.ONLY USE
OPTIONAL EQUIPMENT MADE OR APPROVED BY THE MANUFACTURER AND SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT, AND HAVE IT INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION.
d Vor Zugriff auf die klemmen müssen die Stromkreise der Spannungsversorgung unterbrochen werden.
UNSACHGEMÄSSES INSTALLIEREN ODER ANBRINGEN VON ANLAGE ODER SONDERZUBEHÖR KANN ZU STROMSCHLAG, KURZSCHLUSS, LECKAGEN, BRAND UND ANDEREN SCHÄDEN FÜHREN.
VERWENDEN SIE AUSSCHLIESSLICH VOM HERSTELLER GEFERTIGTES ODER ZUGELASSENES SONDERZUBEHÖR, DAS SPEZIELL FÜR DIE ANLAGE ENTWICKELT WURDE UND LASSEN SIE ES
VON EINEM FACHMANN INSTALLIEREN.
SOLLTEN SIE FRAGEN ZUR INSTALLATION ODER ZUM BETRIEB HABEN, WENDEN SIE SICH BITTE AN IHREN HÄNDLER. ER BERÄT UND INFORMIERT SIE.
f Avant d'accéder aux moyens de raccordement, tous les circuits d'alimentation doivent être déconnectés.
L'INSTALLATION OU LA FIXATION INCORRECTE DE L'ÉQUIPEMENT OU DE L'ÉQUIPEMENT EN OPTION PEUT ENTRAÎNER UNE DÉCHARGE ÉLECTRIQUE, UN COURT-CIRCUIT, DES FUITES, UN
INCENDIE OU D'AUTRES DOMMAGES. UTILISEZ UNIQUEMENT L'ÉQUIPEMENT EN OPTION FABRIQUÉ OU APPROUVÉ PAR LE FABRICANT ET SPÉCIALEMENT CONÇU POUR ÊTRE UTILISÉ AVEC
L'ÉQUIPEMENT ET CONFIEZ L'INSTALLATION À UN PROFESSIONNEL.
EN CAS DE DOUTES QUANT AUX PROCÉDURES D'INSTALLATION OU D'UTILISATION, PRENEZ TOUJOURS CONTACT AVEC VOTRE DISTRIBUTEUR POUR OBTENIR DES CONSEILS ET DES
INFORMATIONS.
l Voordat u zich toegang tot de klemmen verschaft dienen alle spanningscircuits afgesloten te worden.
EEN VERKEERDE INSTALLATIE OF BEVESTIGING VAN APPARATUUR OF OPTIONELE APPARATUUR KAN EEN ELEKTRISCHE SCHOK, EEN KORTSLUITING, LEKKEN OF BRAND VEROORZAKEN OF
NOG ANDERE BESCHADIGINGEN. GEBRUIK UITSLUITEND DOOR DE FABRIKANT VERVAARDIGDE OF GOEDGEKEURDE OPTIONELE APPARATUUR DIE SPECIFIEK WERDEN ONTWORPEN OM MET
HET TOESTEL TE WERKEN EN LAAT EEN ERVAREN TECHNICUS DEZE APPARATUUR MONTEREN.
NEEM VOOR ADVIES EN INFORMATIE STEEDS CONTACT OP MET UW VERDELER WANNEER U NIET ZEKER BENT HOE TE MONTEREN OF TE GEBRUIKEN.
e Antes de acceder a los terminales se deben cortar todos los circuitos de alimentación eléctrica.
UNA INSTALACIÓN O UN MONTAJE INCORRECTOS DE LOS EQUIPOS O DE EQUIPOS OPCIONALES PUEDE PROVOCAR DESCARGAS ELÉCTRICAS, CORTOCIRCUITOS, FUGAS, INCENDIOS U
OTROS DAÑOS. UTILICE SOLO EQUIPOS OPCIONALES DEL FABRICANTE O QUE CUENTEN CON SU AUTORIZACIÓN Y DISEÑADOS ESPECÍFICAMENTE PARA ESTE EQUIPO, Y DEJE SIEMPRE SU
INSTALACIÓN EN MANOS DE UN PROFESIONAL.
SI NO ESTÁ SEGURO DE LOS PROCEDIMIENTOS DE INSTALACIÓN O DE UTILIZACIÓN, PÓNGASE EN CONTACTO CON SU DISTRIBUIDOR PARA QUE LE ACONSEJE O LE AMPLÍE LA INFORMACIÓN.
i Prima di accedere ai terminali, occorre interrompere l'alimentazione di tutti i circuiti dell'unità.
L'INSTALLAZIONE O IL COLLEGAMENTO NON CORRETTI DELL'APPARECCHIO O DELLE APPARECCHIATURE OPZIONALI POTREBBE DARE LUOGO A FOLGORAZIONI, CORTOCIRCUITI, PERDITE,
INCENDI O ALTRI DANNI. UTILIZZARE ESCLUSIVAMENTE LE APPARECCHIATURE OPZIONALI FABBRICATE O APPROVATE DAL COSTRUTTORE E SPECIFICATAMENTE PROGETTATE PER L'USO CON
L'APPARECCHIO, E FARLE INSTALLARE DA UN TECNICO PROFESSIONISTA.
IN CASO DI DUBBI SULLE PROCEDURE D'INSTALLAZIONE O SULL'UTILIZZO, CONTATTARE SEMPRE IL PROPRIO RIVENDITORE PER AVERE SUGGERIMENTI E INFORMAZIONI.
g
p Antes de obter acesso aos terminais, todos os circuitos de alimentação eléctrica devem ser interrompidos.
A INSTALAÇÃO OU FIXAÇÃO INADEQUADA DO EQUIPAMENTO OU DO EQUIPAMENTO OPCIONAL PODE PROVOCAR CHOQUES ELÉTRICOS, CURTOS-CIRCUITOS, FUGAS, INCÊNDIOS OU OUTROS
DANOS. UTILIZE APENAS O EQUIPAMENTO OPCIONAL FEITO E APROVADO PELO FABRICANTE E ESPECIFICAMENTE CONCEBIDO PARA UTILIZAÇÃO COM O EQUIPAMENTO E ASSEGURE-SE DE
QUE É INSTALADO POR UM PROFISSIONAL.
SE TIVER DÚVIDAS SOBRE OS PROCEDIMENTOS DE INSTALAÇÃO OU UTILIZAÇÃO, CONTACTE SEMPRE O SEU REPRESENTANTE PARA OBTER ESCLARECIMENTOS E INFORMAÇÕES.
ADDENDUM BOOK FOR
OPTIONAL EQUIPMENT
U W Q S N J M C Y H R O K B X T V ; -
Unit + digital I/O PCB
Unit + demand PCB
Unit + wired room thermostat
Unit + wireless room thermostat
Unit + heat pump convector
Unit + remote indoor/outdoor sensor
Unit + WLAN module
Unit + LAN adapter
Unit + domestic hot water tank
4P629082-1C
on rear cover
2023.05

Publicité

loading

Sommaire des Matières pour Daikin Altherma BRP069A62

  • Page 1 ADDENDUM BOOK FOR OPTIONAL EQUIPMENT Unit + digital I/O PCB Unit + demand PCB Unit + wired room thermostat Unit + wireless room thermostat Unit + heat pump convector Unit + remote indoor/outdoor sensor Unit + WLAN module Unit + LAN adapter Unit + domestic hot water tank a Before obtaining access to terminals, all power supply circuits must be interrupted.
  • Page 2 a Addendum book for optional equipment d Ergänzendes Buch für optionale Ausstattungen f Ouvrage complémentaire pour l'équipement en option l Addendum boek voor optionele apparatuur e Anexo para equipo opcional i Manuale di supplemento per le apparecchiature opzionali g Συμπληρωματικό εγχειρίδιο για τον προαιρετικό εξοπλισμό p Livro de anexo para equipamento opcional u Приложение...
  • Page 3 EHBH/X EHVH/X EHVZ + EKRP1HBAA X2A/CN2 OFF ON X1A/CN1 X1A/CN1 YC Y1 Y2 Y3 Y4 EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* X2A/CN2 OFF ON X1A/CN1 YC Y1 Y2 Y3 Y4 90° 90° EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* X33A X33A X33A X33A X2A/CN2 X2A/CN2 X2A/CN2 X2A/CN2...
  • Page 4 EHBH/X EHVH/X EHVZ + EKRP1AHTA EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* 180° EHBH/X*E* EHVH/X*(U)*E* EHVZ*E* X85A X80A X80A X85A X85A X85A X80A X80A EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* EKRP1AHTA Demand PCB Addendum book for optional equipment Unit + digital I/O PCB, demand PCB, wired room thermostat, wireless room thermostat, heat pump convector, remote indoor/outdoor sensor, WLAN module, LAN adapter, domestic hot water tank EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* 4P629082-1C –...
  • Page 5 EHBH/X EHVH/X EHVZ + EKWUFHTA1V3 MAIN LWT ZONE ADD. LWT ZONE EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* 30 35 30 35a 230 V AC 230 V AC EKWUFHTA1V3 EKWUFHTA1V3 Only for reversible models Only for reversible models EKWUFHTA1V3 EKWUFHTA1V3 EHBH/X...
  • Page 6 EHBH/X EHVH/X EHVZ + EKRTR1+EKRTETS / EKRTRB+EKRTETS EKRTR1+EKRTETS EKRTRB+EKRTETS EKRTR1 EKRTETS EKRTRB EKRTETS MAIN LWT ZONE ADD. LWT ZONE EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* 35 34 31 30 35a 34a 31 30 –t° –t° –t° –t°...
  • Page 7 EHBH/X EHVH/X EHVZ + FWXV/T/M10~20ATV3 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* + FWXV + EKPCBO / EKRTCTRL2 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* MAIN LWT ZONE EHBH/X*E* / EHVH/X*E* / EHVZ*E* [2.7] [2-0C] Emitter type 1: Fancoil unit [2.9] [C-07] Control 0: Leaving water ADD.
  • Page 8 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* + FWXV + EKRTCTRL1 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* MAIN LWT ZONE [2.7] [2-0C] Emitter type 1: Fancoil unit [2.9] [C-07] Control 1: External room thermostat ADD. LWT ZONE [2.A] [C-05] Thermostat type 1: 1 contact...
  • Page 9 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* + FWXV/T/M + EKWHCTRL0 + EKWHCTRL1 EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* MAIN LWT ZONE EHBH/X*E* / EHVH/X*(U)*E* / EHVZ*E* [2.7] [2-0C] Emitter type 1: Fancoil unit [2.9] [C-07] Control 1: External room thermostat [2.A] [C-05] Thermostat type 1: 1 contact ADD.
  • Page 10 EHBH/X EHVH/X EHVZ + KRCS01-1 / EKRSCA1 KRCS01-1 + EKRSCA1 10 mm EHBH/X*E* KRCS01-1 / EKRSCA1 EHVH/X*(U)*E* EHVZ*E* Addendum book for optional equipment Unit + digital I/O PCB, demand PCB, wired room thermostat, wireless room thermostat, heat pump convector, remote indoor/outdoor sensor, WLAN module, LAN adapter, domestic hot water tank EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* 4P629082-1C –...
  • Page 11 EHVH/X EHVZ + BRP069A71 X 1 A X 1 4 Y BRP069A71 4× 4× BRP069A71 2× Unit + digital I/O PCB, demand PCB, wired room thermostat, wireless room thermostat, heat pump Addendum book for optional equipment convector, remote indoor/outdoor sensor, WLAN module, LAN adapter, domestic hot water tank EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* 4P629082-1C –...
  • Page 12 EHBH/X + BRP069A71 2× X 1 A X 1 4 Y BRP069A71 4× 4× BRP069A71 2× . . . Addendum book for optional equipment Unit + digital I/O PCB, demand PCB, wired room thermostat, wireless room thermostat, heat pump convector, remote indoor/outdoor sensor, WLAN module, LAN adapter, domestic hot water tank EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* 4P629082-1C –...
  • Page 13 EHVH/X EHVZ + BRP069A62 BRP069A62 EHVH/X*(U)*E* + EHVZ*E* BRP069A62 1112 EHBH/X + BRP069A62 BRP069A62 EHBH/X*E* BRP069A62 10 11a X13A L N PE Unit + digital I/O PCB, demand PCB, wired room thermostat, wireless room thermostat, heat pump Addendum book for optional equipment convector, remote indoor/outdoor sensor, WLAN module, LAN adapter, domestic hot water tank EHBH/X*E* + EHVH/X*(U)*E* + EHVZ*E* 4P629082-1C –...
  • Page 14 EHBH/X + EKHWS(U) EHBH/X BSH > X7M EKHWS(U)*D* SWB: K3M+X7M X13A N PE K3M+X7M A1(13) A2(14) X13A BSH > K3M N PE Q1DI L/L1 N/L2 L1/L2/L3 1N~ or 3~, 50 Hz 3N~, 50 Hz 230 V AC 400 V AC 3 kW 3 kW Addendum book for optional equipment...
  • Page 15 11a 12 13 14a X13A N PE >50 mm X2M.12 X2M.13 >50 mm X2M.14a (SPST) >50 mm BSH > K3M BSH > X7M X9A.1 –t° X9A.2 Q1DI L1/L2/L3 L/L1 N/L2 3N~, 50 Hz 1N~ or 3~, 50 Hz 400 V AC 230 V AC 3 kW 3 kW...
  • Page 16 EHBH/X + EKHWP + EKBH3SD EHBH/X BSH > X7M GRN/YLW X7M.PE X7M.N EKHWP <70°C) X7M.L (K3M, X7M) EKEPRHLT* EKBH3SD EKBH3SD SWB: K3M+X7M X13A N PE A1(13) A2(14) X13A BSH > K3M N PE Q1DI L/L1 N/L2 L1/L2/L3 1N~ or 3~, 50 Hz 3N~, 50 Hz 230 V AC 400 V AC...
  • Page 17 12 13 14a X13A N PE >50 mm X2M.12 X2M.13 >50 mm X2M.14a (SPST) >50 mm BSH > K3M BSH > X7M X9A.1 –t° X9A.2 Q1DI L1/L2/L3 L/L1 N/L2 3N~, 50 Hz 1N~ or 3~, 50 Hz 400 V AC 230 V AC 3 kW 3 kW...
  • Page 20 4P629082-1C 2023.05...