RELAY KIT INSTALLATION FOR MULTIPLE UNIT CONTROL
OPTIONS CL31 AND CL32 FOR ELECTRIC UNIT HEATER MODEL EUH,
DESTRATIFICATION FAN MODEL H, GAS-FIRED DOWNFLOW HEATER MODEL LDAP,
AND GAS-FIRED UNIT HEATER MODELS UBX, UBXC, UBZ, UDX, UDXC, UDZ, AND UEZ
• DO NOT use these multiple unit control options with a two-stage thermostat.
• These instructions are designed to assist a qualified electrician in installing this multiple unit
control kit. For maximum safety, the control is installed in the low voltage circuit. Interruption
of the supply voltage is not recommended.
• All electrical wiring and connections, including electrical grounding, MUST be in accordance
with the National Electric Code (ANSI/NFPA No. 70, latest edition) or, in Canada, the Canadian
Electric Code (Part 1, CSA C.22.1, latest edition). In addition, the installation must comply with
local ordinances and applicable gas company requirements.
• These relay kits are designed to permit the control of up to five units (one control unit and up to four additional
non-control units) with one single-stage thermostat or with a time clock and one or more single-stage thermostats.
• Refer to the installation manual provided with the unit for important safety information.
NOTE: Option CL31 includes components for one control unit and one additional unit. Option
CL32 includes components for each additional non-control unit. Not all kit components will be
used on all models.
Ensure that all components listed in
Item
Component
Description
No.
1
Relay
Assembly
2
Screw
3
Cable clamp
3/16
4
Label
Wiring diagram
30VA
5
Transformer
40VA
6
Wiring harness Assembly
*
Includes relay(s) (PN 18549), 24VAC DPDT plug(s) (PN 211411), and socket(s) with wires and terminals (PN 211415). If replacing a
previously-used relay only (PN 98118) on an LDAP unit, order replacement kit PN 263527.
**
Includes relay (PN 18549) and bracket.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
⚠ CAUTION ⚠
KIT COMPONENTS
Table 1
Table 2
or
Table 1. Kit Components (Models EUH and LDAP)
EUH
LDAP
(208V-240V)
1041280
1042927
*
208365
(2)
38529 (4)
621709 (1)
Revision: OPT-CL31,32 (02-25) 1042699-E
Supersedes: OPT-CL31,32 (11-24) 1042699-D
are available before beginning installation.
Option
CL31
Model
EUH
EUH
(277V)
(480V)
Kit PN
1047587
1042928
Component PN (Quantity)
**
197157
(2)
195249 (4)
16228 (2)
197164 (2)
1042451 (1)
202661 (1)
1042929 (1)
CL32
EUH
LDAP
(600V)
1047588
1041286
*
208365
(1)
38529 (2)
197164 (1)
258912 (1)
EUH
1041287
**
197157
(1)
195249 (2)
16228 (1)

Publicité

loading

Sommaire des Matières pour Reznor OPT-CL31

  • Page 1 Revision: OPT-CL31,32 (02-25) 1042699-E Supersedes: OPT-CL31,32 (11-24) 1042699-D RELAY KIT INSTALLATION FOR MULTIPLE UNIT CONTROL OPTIONS CL31 AND CL32 FOR ELECTRIC UNIT HEATER MODEL EUH, DESTRATIFICATION FAN MODEL H, GAS-FIRED DOWNFLOW HEATER MODEL LDAP, AND GAS-FIRED UNIT HEATER MODELS UBX, UBXC, UBZ, UDX, UDXC, UDZ, AND UEZ ⚠...
  • Page 2 Figure 1, DETAIL B. (3) Connect wires for transformer (5) in accordance with (4) Install control compartment access panel. 277V 480V 600V DETAIL A DETAIL B Figure 1. Transformer Location (Typical) and Wiring—Model EUH (Refer to Table OPT-CL31,32 (02-25) 1042699-E...
  • Page 3 For electric unit heater model EUH (see Figure (1) At rear of heater, remove and save screws from edge of cabinet bottom. (2) Secure relay assembly (1) as shown using existing screws. EXISTING SCREWS Figure 3. Relay Installation—Model EUH (Refer to Table OPT-CL31,32 (02-25) 1042699-E...
  • Page 4 (1) Remove control compartment access panel from main heat section. (2) Position relay assembly (1) as shown in Figure 5 and secure using screws (2). (3) Install control compartment access panel. Figure 5. Relay Installation—Model LDAP (Refer to Table OPT-CL31,32 (02-25) 1042699-E...
  • Page 5 4. Determine control wiring configuration. Do not exceed length and distance listed in Table Table 3. Control Wiring Specifications Maximum Distance Maximum Length Size (AWG) Feet (Meters) 2100 (640) 1050 (320) 1300 (457) 650 (198) 500 (152) 250 (76) For complete circuit. OPT-CL31,32 (02-25) 1042699-E...
  • Page 6 Wipe surface with clean, dry cloth. d. Remove label backing and adhere label to unit. 7. Restore system to service: a. For gas-fired units, turn ON gas and electric power. For electric units, turn ON electric power. b. Check for proper operation. OPT-CL31,32 (02-25) 1042699-E...
  • Page 7 NOTES OPT-CL31,32 (02-25) 1042699-E...
  • Page 8 Specifications and illustrations subject to change without notice or incurring obligations. Latest version of this manual is available at www.reznorhvac.com. ©2025 Reznor LLC, O’Fallon, MO. All rights reserved. OPT-CL31,32 (02-25) 1042699-E...
  • Page 9 Révision : OPT-CL31,32 (02-25) 1042699-E Remplace : OPT-CL31,32 (11-24) 1042699-D INSTALLATION DU KIT DE RELAIS POUR LE CONTRÔLE DE PLUSIEURS UNITÉS OPTIONS CL31 ET CL32 POUR CHAUFFAGE ÉLECTRIQUE MODÈLE EUH, VENTILATEUR DE DÉSTRATIFICATION MODÈLE H, CHAUFFAGE À GAZ À FLUX DESCENDANT MODÈLE LDAP ET CHAUFFAGE À...
  • Page 10 (3) Branchez les fils du transformateur (5) conformément à la Figure 1, DÉTAIL B. (4) Installer le panneau d’accès au compartiment de commande. 277V 480V 600V DÉTAIL A DÉTAIL B Figure 1. Emplacement du transformateur (typique) et câblage—modèle EUH (reportez-vous au Tableau OPT-CL31,32 (02-25) 1042699-E...
  • Page 11 (1) À l’arrière du radiateur, enlevez et gardez les vis du bord inférieur de l’armoire. (2) Fixez l’ensemble de relais (1) tel qu’indiqué à l’aide des vis existantes. EXISTANTES Figure 3. Installation de relais—modèle EUH (reportez-vous au Tableau OPT-CL31,32 (02-25) 1042699-E...
  • Page 12 (2) Placez l’ensemble de relais (1) tel qu’illustré à la Figure 5 et fixez-le à l’aide des vis (2). (3) Installer le panneau d’accès au compartiment de commande. Figure 5. Installation de relais—modèle LDAP (reportez-vous au Tableau OPT-CL31,32 (02-25) 1042699-E...
  • Page 13 4. Déterminer la configuration du câblage de contrôle. Ne pas dépasser la longueur et la distance indiquées dans Tableau Tableau 3. Spécifications du câblage de contrôle Distance maximale Longueur maximale Taille (AWG) Pieds (mètres) 2100 (640) 1050 (320) 1300 (457) 650 (198) 500 (152) 250 (76) Pour circuit complet. OPT-CL31,32 (02-25) 1042699-E...
  • Page 14 Retirez l’étiquette à l’arrière et collez-la sur l’unité. 7. Restaurer le système en service : a. Pour les unités au gaz, allumez le gaz et l’électricité. Pour les unités électriques, mettez sous tension. b. Vérifiez le bon fonctionnement. OPT-CL31,32 (02-25) 1042699-E...
  • Page 15 REMARQUES OPT-CL31,32 (02-25) 1042699-E...
  • Page 16 Spécifications et illustrations sujettes à changements sans préavis ou sans aucune obligation. La dernière version de ce manuel est disponible sur www.reznorhvac.com. ©2025 Reznor LLC, O’Fallon, MO. Tous droits réservés. OPT-CL31,32 (02-25) 1042699-E...