Télécharger Imprimer la page

Fields Of Application - Watts MH Série Manuel D'installation Et D'utilisation

Publicité

UK
Version MH
Maximum pressure:
Operating temperature:
Range of adjustment:
Kvs:
Version MH20
Maximum pressure:
Operating temperature:
Range of adjustment:
Kvs:

FIELDS OF APPLICATION

Installing the "MH" series valve on the distribution
manifold of a radiant system, allows, once the
initial calibration has been performed, ensuring a
correct distribution of the flow rate with immediate
comfort and reduced consumption.
OPERATION
"MH" series balancing valves for radiant systems
work by maintaining constant the differential pres-
sure on the radiant distribution manifolds.
Pressure difference may vary significantly as a
result of load variations, both external and inter-
nal, to the radiant system. Through the balancing
piston, the "MH" series valve allows levelling out
any imbalances, maintaining the pre-set differen-
tial pressure constant.
FITTING
The "MH" series valve features a G1" (2) idle
nut that allows it to be connected to the return
manifold placed in the radiant system's distribu-
tion box.
The capillary tube supplied must be connected
between the pressure plug (5) positioned on the
bottom cap of the valve, and the pressure plug
placed on the ball valve on the inlet manifold.
CALIBRATION
To calibrate a system with more than one manifold
with MH, implement the following procedure
1. Connect the MH series valve to the return
manifold with capillary tube provided
2. Set the pump (or pumps) in constant speed
according to the maximum flow rate and
maximum pump head needed (in the case of
new installations or installations with inverter
pumps).
The descriptions and photographs contained in this product specification sheet are supplied by way of information only and are not binding. Watts
Industries reserves the right to carry out any technical and design improvements to its products without prior notice. Warranty: All sales and contracts
for sale are expressly conditioned on the buyer's assent to Watts terms and conditions found on its website at www.wattswater.eu. Watts hereby objects
to any term, different from or additional to Watts terms, contained in any buyer communication in any form, unless agreed to in a writing signed by
an officer of Watts.
MH-MOI-IT-W-ML-11-20-Rev0
10 bar
5° - 80°C
15-50 KPa
5.6
10 bar
5° - 80°C
20-50 KPa
5.6
3. Go to the nearest manifold according to the
pump.
4. All loops must be open
5. Start the system (at this point the sections will
be unbalanced)
6. Locate the unfavourable section, (the one
with a lower flow rate).
7. Turn the valve's control knob (4) to bring the
value of the unfavourable section flow to the
desired value
Is the flow
indicator
moving?
YES
Go to point 8
Turn counterclockwise the knob till full
opening.
Set the Dp design turning the knob
DP setting=17+3,5x number of turns (kPa)
Example 2 turns
Dp setting= 17+3,5x2=24 kPa
8. Then adjust the columns of the manifold
valves to vary the flow rate of the other sec-
tions
9. Fasten the control knob by using the appro-
priate security dowel (3)
10. Calibrate next manifold (nearest second one
according to the pump) with the same pro-
cess.
11. Keep on calibrating the following manifolds in
the order according to the pump.
12. Set the pump in the self-adjusted mode
operation.
ALL INSTALLATION, REARMING, CALIBRATION AND
MAINTENANCE OPERATIONS MUST BE CARRIED OUT
SOLELY BY QUALIFIED PERSONNEL.
NO
Increase
the pump
speed
YES
Is the flow
indicator
moving?
NO
Traditional setting
Rev. A 11/2020
3

Publicité

loading