External Devices - Steute Rf 96 St Sw868 Instructions De Montage Et De Câblage

Table des Matières
RF 96 ST SW868/SW915/SW917/SW922
Montage- und Anschlussanleitung / Funk-Universalsender
Mounting and wiring instructions / Wireless universal transmitter
Instructions de montage et de câblage / Emetteur universel sans fil
Istruzioni di montaggio e collegamento / Trasmettitore universale wireless
Instruções de montagem e instalação / Transmissor universal sem fio
English
Use of the mounting and wiring instructions
All actions described in these instructions may only be performed by
qualified persons who have been trained and authorised by the
operating company.
1. Read and understand these mounting and wiring instructions.
2. Comply with the valid occupational safety and accident prevention
regulations.
3. Install and operate the device.
Selection and installation of devices and their integration in control
systems demand qualified knowledge of all the relevant laws, as well
as the normative requirements of the machine manufacturer. In case
of doubt, the German language version of these instructions shall
prevail.
Scope of delivery
Device, mounting and wiring instructions, packaging.
Intended use
The device is used for radio transmission of switching information.
A telegram is sent to the receiver when a switch is closed or opened
and when a threshold is exceeded or not reached. The receiver must
conform to the sWave ® protocol of the steute modules.
Mounting and wiring
Mount the device on an even surface. Install the device according to
the mounting and wiring instructions of the receiver. The wireless
range depends heavily on the local conditions. Conductive materials
may strongly affect the radio signal. This also includes thin foils, e.g.
aluminium laminations on insulation materials.
Assignment of locations and radio frequencies:
Device type
Radio frequency
SW868
868.3 MHz
SW915
915.0 MHz
SW917
917.0 MHz
SW922
916.5 MHz

External devices

Connect external devices to M12 connector. To connect external devic-
es (sensors or switches): see section »Connecting external devices«.
When installing the external device, follow its installation instructions.
Location
According to
EU
2014/53/EU (RED)
USA
FCC
Canada
IC
Mexico
IFT
Brazil
ANATEL
Japan
ARIB STD-T108
Connectable devices:
Device
0.3 m
RF IS M8 nb-ST
RF IS M12 nb-ST
RF IS M18 nb-ST
RF IS M30 nb-ST
RF RC 20 1S-ST
1335490
connecting cable,
open wire ends
Other connectable devices: Switches with gold contacts; switches with
hermetically sealed contacts. Use the connection cable (1215497)
for connection.
Design of wireless range
The radio signal is attenuated on the way from the transmitter to the
receiver. In addition, the radio signal is influenced by obstacles. The
degree of attenuation depends on the material of the obstacle.
The following tables serve as a guide.
Penetration of radio signals:
Material
wood, gypsum, glas uncoated
brick stone, press boards
armoured concrete
metal, aluminium lamination, water
Typical ranges:
Location
in free field (SW868/915/917)
in free field (SW922)
indoors (SW868/915/917)
indoors (SW922)
Field strength meter for range test:
Transmitter
Device
SW868
swView 868 MHz
SW915
swView 915 MHz
SW917/SW922
3 / 20
Article no. (Cable length)
0.5 m
1 m
2 m
1470040
1373082
1305745
1228522
1356467
1189974
1261564
on request
1189975
1260490
1228548
1189976
1215497
Penetration
90...100 %
65...95 %
10...90 %
0...10 %
Wireless range
(approx.)
450 m
150 m
40 m
20 m
Article no.
1190393
1221794
on request
Table des Matières
loading