Service
ICAD
Description
parameter
OD %
¡50
AI [mA]
¡51
AI [V]
¡52
AO [mA]
¡53
DI
¡54
DO Close
¡55
DO Open
¡56
DO Alarm
¡57
Display mP SW ver.
¡58
Motor mP SW ver.
¡59
Reset to factory setting:
1. Remove the power supply.
2. Activate down arrow and up arrow push buttons at the same time.
3. Connect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD (fig. 2) is alternating between showing: CA and A1 the
factory resetting is complete.
© Danfoss | Climate solutions | 2023.04
Factory
Min
Max
Stored
Unit Password Comments
Setting
0
100
-
0
100
-
0
100
-
0
100
-
0
1
-
0
1
-
0
1
-
0
1
-
0
100
-
0
100
-
%
-
ICM valve Opening Degree / CVE pressure setting
mA
-
AI signal
V
-
AI signal
mA
-
A0 signal
DI signals. Depending of ¡02
If ¡02 = 2, one digits are shown. See fig. 8
0 : DI1 = OFF
1 : DI1 = ON
-
-
If ¡02 = 3, two digits are shown. See fig. 9
00 : DI1 = OFF, DI2 = OFF
10 : DI1 = ON, DI2 = OFF
01 : DI1 = OFF, DI2 = ON
11 : DI1 = ON, DI2 = ON
-
-
DO Closed status. ON when OD < 3 %
-
-
DO Open status. ON when OD > 97 %
-
-
DO alarm status. ON when a Alarm is detected
-
-
Software version for display microprocessor
-
-
Software version for motor microprocessor
AN19798642980802-001001 | 7