Télécharger Imprimer la page

Tefcold SE10-45 Mode D'emploi page 29

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Dixell XR20-30CX (SE-45 Series)
PAR.
DESCRIPTION
Set
Set point
Hy
diFferential. Relay compressor tripping differential. The compressor stops on
reaching the Setpoint value, and restarts at temperature equal to the Setpoint plus
the value of the differential.
LS
Lower SEt. Minimum possible setpoint value.
US
Higher SEt. Maximum possible setpoint value.
Ot
CAlibration 1.Calibration 1. Positive or negative temperature value added to the
value read by probe 1, based on "ot" parameter settings.
P2P
Second probe presence: n=not present, y=present
oE
CAlibration 2.Calibration 2. Positive or negative temperature value added to the
value read by probe 2, based on "P2" parameter settings.
odS
delay (at) On compressor. Delay time in activating the compressor relay after
switch-on of instrument.
AC
Anti short cycle delay
CON
On time (compressor). Compressor activation time in the event of faulty probe.
COF
OFF time (compressor). Compressor in disabled state time in the event of a faulty
probe.
CF
Measurement units: °C=Celsius, °F=Fahrenheit
rES
Resolution (only for °C): dE=decimal between -9.9 and 9,9; in=integer
Lod
Default display: P1=thermostat probe, P2=evaporator probe, SP=Set point
td
defrost type. Type of defrosting.
El = electric defrost.
in = reverse cycle defrost (hot gas)
dtE
Defrost termination temp.
idF
defrost interval time. Interval between the start of two successive defrosting
operations.
MdF
Max length for defrost
dFd
Display during defrost: rt=real temp. it=start defrost temp., St=Set point, dF=llabel
Df
dAd
Max display delay after defrost
dAF
Defrost delay after fast freezing
ALc
Temperature alarm configuration: rE=relative to SET, Ab=absolute
ALU
Higher ALarm. Maximum temperature alarm. Temperature value.
which if exceeded in an upward direction triggers the activation of the alarm signal.
ALL
Lower ALarm. Minimum temperature alarm. Temperature value.
which if exceeded in a downward direction, triggers the activation of the alarm
signal.
ALd
Temperature alarm delay
dAO
Exclusion of temperature alarm at startup.
PbC
Kind of probe
RANGE
DEFAULT
LS-US
-45
0.1...25.0
2,0
-55.0...HSE
-45
LSE..302
-5,0
-9.9...9.9
0
n/y
N
-9.9...9.9
0
0...99
2
0...50
5
0...99
10
0...99
10
°C/°F
°C
dE-in
dE
P1,P2,SP
P1
EL/in
In
-50...50
6
0...99
0
0...99
0
Rt/it/SP/dF
St
0...255
1
0...23
0
rE/Ab
rE
AL...99
10
-55...AU
-1
0...99
20
0..23
1
Ptc/ntc
Ntc
U.M.
°C/°F
°C/°F
°C/°F
°C/°F
°C/°F
flag
°C/°F
min
Min
min
min
°C/°F
flag
flag
flag
°C/°F
hours
min
flag
Min
hours
Flag
°C/°F
°C/°F
min
hour
flag
29

Publicité

loading

Ce manuel est également adapté pour:

Se20-45Se30-45Se40-45