Connections; Power Supply; Gas Valve; External Alarm - Vetus GD1000 Manuel D'utilisation Et Instructions D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
ENGLISH

5.3 Connections

Connect the gas detector as shown in '8 Wiring diagram'.

5.3.1 Power supply

The gas detector is suitable for both 12 and 24 Volt.
The fuse in the plus wire of the gas detector only protects the gas detector itself and
does not protect any gas valve, alarm or fan connected!

5.3.2 Gas valve

An electrically operated gas valve can be connected to the output 'VALVE'. The gas
valve is incorporated in the gas supply line. If there is an alarm situation the valve will be
closed automatically and shut off the gas supply to the installation.
The gas valve must operate at the same voltage as the power supply to the installation,
either 12 or 24 volt direct current respectively. The output 'VALVE' is suitable for a gas
valve requiring a current of maximum 1 A. Fit a 1 A fuse in the plus wire to the gas valve.
NB: the gas detector switches the minus connection (-, earth) to the gas valve!

5.3.3 External Alarm

An external alarm (for example, a hooter or buzzer) or a contact for an alarm system can
be connected to the output 'ALARM'.
If there is an alarm situation the external alarm will be switched on automatically.
The external alarm (hooter or buzzer) must operate at the same voltage as the power
supply to the installation, either 12 or 24 volt direct current respectively.
The output 'ALARM' is suitable for a hooter or buzzer requiring a current of maximum 1
A. Fit a 1 A fuse in the plus wire to the hooter or buzzer. NB: the gas detector switches
the minus connection (-, earth) to the hooter or buzzer!
5.3.4 Ventilator
An electric fan can be connected to the output 'FAN'. The fan is to replenish the air in
the room being monitored.
If there is an alarm situation the fan will be switched on automatically.
The fan must be ignition protected!
The fan must operate at the same voltage as the power supply to the installation, either
12 or 24 volt direct current respectively.
The output 'FAN' is suitable for a fan requiring a current of maximum 1 A. Fit a 1 A fuse
in the plus wire to the fan. NB: the gas detector switches the minus connection (-, earth)
to the fan!
21
Gas detector GD1000
100105.02

Publicité

Table des Matières
loading

Table des Matières