CAK-PH-A Off pipe cable gland kit and end seal
Installation
Required tools
The following tools are required for installation of the CAK-PH-A Off
pipe cable gland kit and end seal:
 Wire cutters
 Flat screwdriver
 Crimping pliers
Cautions and warnings
WARNING
Risk of fire or electrical shock. De-energize all power circuits before
installation or servicing. Always use ground fault equipment within
the heat tracing system.
 Double-check that all power circuits are de-energized before you
begin your work.
 Make sure that you do not exceed the maximum heating circuit
length for the trace heater type you use. Refer to the design
guide of the heating system.
Preparation of the trace heater
WARNING
Risk of short cuts and/or material damage. Keep the trace heater
ends dry before and during installation. Observe the design guide of
the trace heating system.
 Cut off the trace heater ensuring a straight cut.
21-59CZ-7D0002
 Utility knife
 Needle-nose pliers (2x)
 Tape measure
2 x
1
2
3
Notice Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Installation Instructions
 Select the correct grommet for the trace heater to be connected.
Note the small letter on the grommet:
 "P"-grommet for PSB trace heaters
 "H"-grommet for HSB trace heaters
"P"
 Slide the fixing nut, the sealing and the gland body onto the trace
heater.
 Remove 5 3/4" (145 mm) of the outer jacket on the end of the trace
heater.
"H"
4
5
6