Installation of the end seal
 Cut the trace heater off straight.
 Remove 3/4" (20 mm) of the outer jacket.
 Remove the exposed grounding braid. Make sure that the insula-
tion jacket is not damaged.
 Cut in a triangle (1/4" / 5 mm) between the bus wires.
21-59CZ-7D0002
21
22
23
Notice Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
CAUTION
The silicone adhesive may cause irritation to skin and eyes. Avoid eye
contact. Avoid repeated or prolonged skin contact. In case of contact
with eyes, rinse with water and seek medical advice.
 Put silicone adhesive onto the exposed insulating jacket and into the
end seal.
 Push the end seal onto the end of the trace heater.
NOTICE
Allow the adhesive to cure for 20 minutes, then visually inspect. Full
strength is reached after 24 hours.