INSTALLATION INSTRUCTIONS - SLD2
SLD/CM/4S/AC
(REFERENCE ONLY)
FIXTURE ASSEMBLY
NOTES:
For replacement LED Assemblies and Drivers please contact Current Lighting for any replacement parts.
Contact your local distributor or agent to confirm parts availability prior to ordering replacement parts.
95059205 Rev. A
701 Millennium Boulevard Greenville, SC 29607 (864) 678-1000
SAVE THESE INSTRUCTIONS
(1) PIN AND COTTER
(3) SET SCREWS
TORQUE SCREWS TO
144 IN LBS
WIRE CONNECTORS
(BY OTHERS)
STREET
SIDE
NOTE STREET SIDE LABEL AND ORIENT FIXTURE ACCORDINGLY
Catenary Mount
INSTALLATION STEPS:
1. Turn off all power to the unit and take proper safety
precautions.
2. Follow instructions to mount catnary arm. Thread coupling
adapter into catenary mount and secure with set screw.
3. Remove clevis pin and cotter and set aside. Loosen (3) set
screws in arm coupling.
4. Connect fixture leads to feed wires (Verify supply voltage
against fixture labeling), secure with wire tie or other means
of stress relief to prevent disconnection. Push wires into the
arm.
5. Insert luminaire into arm, line up pin through-holes. Pass
pin through aligned holes. Attach cotter to the end of pin.
6. Apply Loctite 262 to the threads of the set screws. Tighten
set screws evenly in an alternating pattern.
NOTE: The pin will temporarily support the luminaire but the
installation should not be left unattended until the luminaire is
properly secured with screws.
7. Turn on power and test fixture.
8. Installation is complete .
Tools Required:
Hex (Allen) Wrench - 5/32
J-BOX
BLACK
WHITE
GREEN
VIOLET(+)
PINK(-)
NOTE:
VIOLET & PINK WIRES FOR
DIMMING OPTIONAL.
(WIRE COLOR MAY VARY
BASED ON SUPPLY
TO INCOMING
VOLTAGE )
POWER SOURCE
SHEET 3 OF 8
FIXTURE
LINE
COMMON
GROUND
DIM (+)
DIM (-)