ICAR by ORTEA NEXT
NOA = Alarm normally de-energized. The relay is energized when any alarm with the Global alarm property arises.
NCA = Alarm normally energized. The relay is de-energized when any alarm with the Global alarm property arises.
FAN = The relay controls the cooling fan.
MAN = Relay is energized when device is in MAN mode.
AUT = Relay is energized when device is in AUT mode.
A01 ... A12= The relay is energized when the alarm specified is active.
P.19
Setpoint (target value) of the cos. Used for standard applications.
P.20
Language of scrolling alarm messages
12.2

ADVANCED MENU

COD
DESCRIPTION
P.21
Password enable
P.22
User password
P.23
Advanced password
P.24
Wiring type
P.25
Step trimming
P.26
Setpoint clearance +
P.27
Setpoint clearance -
P.28
Step insertion mode
P.29
Cogeneration cos setpoint
P.30
Disconnection sensitivity
P.31
Step disconnection passing in MAN
P.32
Capacitor current overload alarm threshold
P.33
Capacitor overload immediate disconnection threshold
P.34
VT primary
P.35
VT secondary
P.36
Temperature UoM
P.37
Fan start temperature
P.38
Fan stop temperature
P.39
Temperature alarm threshold
P.41
Maximum voltage alarm threshold
P.42
Minimum voltage alarm threshold
P.43
THD V alarm threshold
P.44
THD I alarm threshold
P.45
Maintenance interval
P.46
Bar-graph function
P.47
Default auxiliary measure
P.48
Backlight flashing on alarm
P.49
Serial node address
P.50
Serial speed
P.51
Data format
P.52
Stop bits
P.53
Protocol
P.54
Number of insertions for maintenance
P.21
If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P.22
With P.21 enabled, this is the value to specify for activating user level access. See Password access chapter.
P.23
As for P.22, with reference to Advanced level access. (*) Available value only if the controller is not installed on the ICAR cabinet
P.24
Number of phases of the power correction panel.
P.25
Enables the measurement of the actual power of the step, performed each time they are switched in. The measure is calculated, as the current
measurement is referred to the whole load of the plant. The measured power of the steps is adjusted (trimmed) after each switching and is
displayed on the step life statistic page. When this function is enabled, a 15 sec pause is inserted between the switching of one step and the
following, necessary to measure the reactive power variation.
P.26 – P.27 Tolerance around the setpoint. When the cos is within the range delimited by these parameters, in AUT mode the device does not connect /
disconnect steps even if the delta-kvar is greater than the smallest step
P.28
Selecting mode of steps insertion.
Standard mode - Normal operation with free selection of the steps
Linear mode - the steps are connected in progression from left towards right only following the step number and according to the LIFO (Last In First
Out) logic. The controller will not connect a step when the system steps are of different ratings and by connecting the next step, the set-point value
would be exceeded.
Disc -
As in the Standard mode but with reduced time spent in capacitive
P.29
Setpoint used when the system is generating active power to the supplier (with negative active power / power factor ).
P.30
Disconnection sensitivity. Same as the previous parameter but related to disconnection. If set to OFF the disconnection has the same reaction time
of connection set with the previous parameter.
P.31
If set to ON, when switching from AUT mode to MAN mode, steps are disconnected in sequence.
P.32
Capacitors overload protection Trip threshold (alarm A07), that will arise after an integral delay time, inversely proportional to the overload value.
Note: You can use this protection only if the capacitors are not equipped with filtering devices such as inductors or similar.
P.33
Threshold beyond which the integral delay for tripping of the overload alarm is zeroed, causing the immediate intervention of the A08 alarm.
P.34 – P.35 Data of VTs eventually used in the wiring diagrams.
P.36
Unit of measure for temperature.
P.37 – P.38 Start and stop temperature for the cooling fan of the panel, expressed in the unit set by P.36. The cooling fan is started when the temperature is
>= to P.37 and it is stopped when it is < than P.38.
P.39
Threshold for generation of alarm A08 Panel temperature too high .
P.41
Maximum voltage alarm threshold, referred to the rated voltage set with P.07, beyond which the alarm A06 Voltage too high is generated.
P.42
Undervoltage alarm threshold, referred to the rated voltage set with P.07, below which the alarm A05 voltage too low is generated.
P.43
Maximum installation voltage THD alarm threshold, beyond which the alarm A10 THDV too high is generated.
P.44
Maximum installation current THD alarm threshold beyond which the alarm A05 voltage too low is generated.
PSW
UoM
DEF
Adv
OFF
Usr
001
Adv
002(*)
Usr
3PH
Adv
ON
Usr
0.00
Usr
0.00
Usr
STD
Usr
OFF
Usr
sec
OFF
Usr
OFF
Adv
%
50
Adv
%
83
Usr
V
OFF
Usr
V
100
Usr
°C
Adv
°
25
Adv
°
20
Adv
°
55
Adv
%
110
Adv
%
90
Adv
%
6
Adv
%
12
9000
Adv
h
8760(**)
Usr
Kvar ins/tot
Usr
TPF sett.
Usr
OFF
Usr
01
Usr
bps
9.6k
Usr
8 bit – n
Usr
1
Usr
Modbus RTU
Adv
kcnt
OFF
16 / 40
ALL75 mar19
RANGE
OFF / ON
0-999
0-999
3PH Trifase / 1PH Monofase
ON Abilitato / OFF Disabilitato
0 – 0.10
0 – 0.10
STD Standard / LIN Lineare / DISC
OFF / 0.50 IND – 0.50 CAP
OFF / 1 – 600
OFF
Disabilitato / ON Abilitato
OFF / 0...150
OFF / 0.. 200
OFF / 50-50000
50-500
°C °Celsius / °F Fahrenheit
0 ... 212
0 ... 212
0 ... 212
OFF / 90...150
OFF / 60...110
OFF / 1...250
OFF / 1...250
1 - 30000
Kvar ins/tot / Corr att/nom / Delta kvar att/tot
Delta kvar / V / A / TPF settimanale / THDC /
Temp / THDV / THDI / ROT
OFF / ON
01-255
1.2k / 2.4k / 4.8k / 9.6k / 19.2k / 38.4k
8 bit, no parity
8 bit, odd / 8bit, even
7 bit, odd / 7 bit, even
1-2
Modbus RTU / Modbus ASCII
OFF / 1...60