4. Dimensions and Required Servicing Space of Branch Box
PAC-AK31BC (3-branch type)
450
91
205
73
C
B
A
C
B
A
25
25
25
21
75
75
Type A
Type B
(1)
450
Min. 50
Min. 250
Fig. 4-5
Fig. 4-7
(3)
Min.250
Fig. 4-8
5. Refrigerant piping
* Always follow the specifications written in the installation manual of the outdoor unit. Exceeding these requirements may cause reduced performance of the
equipment, and malfunctions.
4
All manuals and user guides at all-guides.com
320
12
95
280
39
61
79
50 34
200
23
200
Fig. 4-4
(2)
*1
Min.
Min.
250
280
250
A
180-200
B
*3
Fig. 4-6
450
PAC-AK31BC (Fig.4-4)
(mm)
Suspension bolt: W3/8 (M10)
Refrigerant pipe flared connection
A
B
Liquid pipe
ø6.35
ø6.35
Gas pipe
ø9.52
ø9.52
Drain hose size: O.D.20 (VP16)
4.1. Space required for installation and servicing
(1) Front View (Fig. 4-5)
Branch box
On the side of piping
(2) Side View (Fig. 4-6, Fig. 4-7)
For indoor installations
Ceiling board
Maintenance hole
PCB side
*1: A minimum 350 mm is required for 90° bends in refrigerant piping.
Note:
When using the PAC-AK52BC branch box to connect P100 indoor unit(s),
the following procedure is required.
1. Connect the Y-shape connection pipe end(s) to the indoor unit(s).
2. Mount the branch box.
3. Connect the Y-shape connection pipe ends to the branch box.
*2:
is " Min. 200 mm " <recommendation>.
(Premise: The slope of drain piping is securable 1/100 or more. Required
200 mm or more, when not securable.)
In the case of less than 200 mm (for example
work of Branch box from a maintenance hole becomes difficuBefore lt (Only
exchange work of a PCB, linear expansion valve coils, sensors and drain pan is
possible).
*3:
is "
600 mm " <recommendation>.
In the case of " 450", prepare a maintenance hole at a PCB side (as it is shown
in Fig. 4-7), and "Min. 300 mm" is needed as distance
In the case of less than 300 mm (for example
work of Branch box, linear expansion valve coils, sensors, and drain pan from a
maintenance hole becomes difficult (Only exchange work of a PCB is possible).
(3) Top View (Fig. 4-8)
Refrigerant piping
When facing in the opposite direction to the refrigerant piping.
C
To outdoor unit
ø6.35
ø9.52
ø9.52
ø15.88
is 100 mm), the exchange
.
is 100 mm), the exchange

Publicité