Tableau Paramètres Cs Digitech (Miah402) - Radiant R2KA 24 /20 Manuel D'installation Et De Maintenance

Table des Matières

Publicité

2.1.5. TABLEAU PARAMÈTRES CS DIGITECH (MIAH402)
PARAMÈTRE
DESCRIPTION
P00
SÉLECTION MODÈLE CHAUDIÈRE
P01
SÉLECTION TYPE CHAUDIÈRE
P02
SÉLECTION TYPE GAZ
ATTENTION :
LIRE LES INSTRUCTIONS AU CHAPITRE 'TRANSFORMATION
GAZ' AVANT DE MODIFIER CE PARAMÈTRE.
P03
RÉGLAGE DE LA TEMPÉRATURE DE CHAUFFAGE
DANS LE CAS OÙ LA CHAUDIÈRE EST INSTALLÉE ET FAIT
PARTIE D'UN CIRCUIT À BASSE TEMPÉRATURE, INSTALLER
UN THERMOSTAT DE SÉCURITÉ SUR LE FLUX DE CHALEUR
POUVANT STOPPER L'ACTIVITÉ DE LA CHAUDIÈRE EN CAS DE
TEMPÉRATURE ÉLEVÉE DE CELUI-CI. LA SOCIÉTÉ N'ASSUME
AUCUNE RESPONSABILITÉ POUR LES DOMMAGES CAUSÉS AUX
PERSONNES OU LE NON-RESPECT DE CES INSTRUCTIONS.
2. PREMIÈRE MISE EN ROUTE
PLAGE
0 - 10
0 - 5
0 - 1
0 - 1
R2KA 24 /20 - RAD - FRA - Manuel Inst. - 2002.1_CSA
FONCTION
0 - 7 = N.D.
8 = R2K 24 - R2KA 24/8
9 = R2K 34 - R2KA 34/20 - R1K 34/B
10 = R1K 55-R2K 55
0 = INSTANTANÉ > R2K
1 = N.D.
2 = ACCUMULATION > R1K /B
- R2KA
3 = CONFORT ACCUMULATION
> R1K /B - R2KA
4 = CONFORT INSTANTANÉ -
FAST H2O > R2K
5 = SEULEMENT CHAUFFAGE >
R1K 55
0 = GAZ NATUREL (ET RÉGLER
VITESSE VENTILATEUR SUR
LES PARAMÈTRES P10 - P11 -
P12 - P13)
1 = PROPANE (ET RÉGLER
VITESSE VENTILATEUR SUR
LES PARAMÈTRES P10 - P11 -
P12 - P13)
0 = STANDARD 86-167 °F (30-75
°C)
(ÉTABLI PAR DÉFAUT)
1 = RÉDUIT 77-113 °F (25-45 °C)
POUR LES SYSTÈMES AU SOL