Télécharger Imprimer la page

Resol PSW Basic Manuel page 15

Masquer les pouces Voir aussi pour PSW Basic:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1
Overview
The PSW Basic signal converter is used for connecting
speed-controlled high-efficiency pumps with a PWM or
0-10 V control input to a controller without a correspond-
ing output.
• For solar and heating pumps
• PWM or 0-10 V output signal
• Inversion of the output signal possible
• Robust and dripping water protected housing
The PSW Basic pump signal converter converts the 230 V
signal of the controller to which a standard pump had pre-
viously been connected, into a signal that enables speed
control of a HE pump. 1 HE pump per signal converter
connectable.
The following signal conversions are possible:
Input signal
Output signal
On / Off,
Burst / wave packet
Leading-edge phase control
Trailing-edge phase control
Not suitable for heat pumps and DHW exchange controllers
12
All manuals and user guides at all-guides.com
PWM
PWM
0-10 V 0-10 V
inv.
inv.
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Technical data
Inputs: On / Off, bursts / wave packets, phase cutting
Outputs: PWM / 0-10 V
PWM frequency: 625 Hz +-15 %
PWM voltage: 11 V
Power supply: 220 ... 240 V~ (50 ... 60 Hz)
Supply connection: type Y attachment
Power consumption max. 1.5 VA
Mode of operation: 1.Y
Rated impulse voltage: 2,5kV
Functions: signal converter, converting a speed-controlled
230 V signal into a PWM or 0-10 V signal
Housing: plastic
Mounting: Wall mounting
Protection type: IP65 / EN60529
Protection class: II
Ambient temperature: 0 ... 40 °C
Degree of pollution: 2
Dimensions: 80 x 80 x 53 mm

Publicité

loading