Télécharger Imprimer la page

Victron energy Phoenix Compact 12/2000 230V Manuel page 15

Masquer les pouces Voir aussi pour Phoenix Compact 12/2000 230V:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 35
5.5 Configuration with DIP switches
Some settings can be changed with DIP switches
Procedure:
a) Turn the Compact on, preferably without load.
b) Set the dipswitches as required.
c) Store the settings by moving Dip switch 8 to "on" and back to "off".
5.5.1. DIP switch 1 and 2
Default setting: to operate the product with the "On/Off/Charger Only" switch
ds 1: "off"
ds 2: "on"
The default setting is required when using the "On/Off/Charger Only" switch in the front
panel.
Setting for remote operation with a Multi Control Panel:
ds 1: "on"
ds 2: "off"
This setting is required when a Multi Control Panel is connected.
The Multi Control panel must be connected to one of the two RJ48 sockets B, see
appendix A.
Setting for remote operation with a 3-way switch:
ds 1: "off"
ds 2: "off"
This setting is required when a 3-way switch is connected.
The 3-way switch must be wired to terminal L, see appendix A.
Only one remote control can be connected, i.e. either a switch or a remote control
panel.
In both cases the switch on the product itself should be "on".
5.5.2 Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP
switches of a new product are set to 'off', except for DS-2).
DS-1 Panel option
DS-2 Panel option
DS-3 Not used
DS-4 Not used
DS-5 Frequency
DS-6 Search mode
DS-7 Not used
DS-8 Store setting
off
DS-1
on
DS-2
DS-3
DS-4
DS-5
off
DS-6
DS-7
→ ←
DS-8
off
on
off
off
→ ←
DS-1
on
DS-2
off
DS-3
DS-4
DS-5
on
DS-6
on
DS-7
→ ←
DS-8
13

Publicité

loading

Ce manuel est également adapté pour:

Phoenix compact 24/2000 230v