Télécharger Imprimer la page

RIB SUPER 4000 Manuel page 35

Dessins techniques pour les projets
Masquer les pouces Voir aussi pour SUPER 4000:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ALL RADIO CODES FOR TOTAL OPENING CANCELLATION PROCEDURE
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - LED DL12 flashes red for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two
green flashes of LED DL12 and 2 tones of the buzzer.
4 - LED DL12 flashes red again for 10 seonds and you can add new codes as shown above.
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
6 - End of procedure.
RADIO CODES MEMORY FULL INDICATOR (FOR TOTAL OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED
DL12 blinks red for 10 seconds enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
4 - End of procedure.
G - RADIO CODES PROGRAMMING PROCEDURE FOR PEDESTRIAN
OPENING (1000 CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. DL12 flashes green for 10 seconds.
2 - Press the transmitter button (usually channel B) within the allotted 10 seconds. If the
transmitter is properly memorized LED DL12 blinks red and the buzzer emits a tone. The
10 seconds are automatically renewed (DL12 flashes green) in order to memorize next
transmitter.
3 - To finish programming wait 10 seconds, or press the PROG button briefly. The LED DL12
stops flashing.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
ALL RADIO CODES FOR PEDESTRIAN OPENING CANCELLATION PROCEDURE
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 seconds.
2 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two
red flashes of LED DL12 and two tones of the buzzer.
3 - The red LED DL1 remains active and you can add new codes as shown above.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
RADIO CODES MEMORY FULL INDICATOR (FOR PEDESTRIAN OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red
for 10 seconds enabling possible cancellation of codes.
3 - Set DIP 1 to OFF and DIP 3 to OFF.
4 - End of procedure.
H - PROGRAMMING RADIO CODES (FOR R-AUX RELAY) (1000 CODES
MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 seconds.
2 - Press the transmitter button (usually channel C) within the allotted 10 seconds. If the
transmitter is properly memorized LED DL12 blinks green and the buzzer emits a tone.
The 10 seconds are automatically renewed (DL12 flashes orange) in order to memorize
next transmitter.
3 - To finish programming wait 10 seconds, or press the PROG button briefly. The LED DL12
stops flashing.
4 - Reset DIP 1, 2 and 3 to OFF.
5 - End of procedure.
RADIO CODES CANCELLATION PROCEDURE (FOR R-AUX RELAY)
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. LED DL12 flashes green for 10
seconds.
2 - During these 10 seconds press and hold the PROG button for 5 seconds. Memory
cancellation is indicated by two green flashes of LED DL12 and two tones of the buzzer.
3 - LED DL12 blinks orange again for 10 seconds and you can add new codes as shown
above.
4 - Re-Set DIP 1, 2, 3 to OFF.
5 - End of procedure.
RADIO CODES MEMORY FULL INDICATOR (FOR R-AUX RELAY)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red
for 10 seconds enabling possible cancellation of codes.
3 - Re-Set DIP 1, 2, 3 to OFF.
4 - End of procedure.
FUNCTIONING OF CONTROL ACCESSORIES
STEP-BY-STEP BUTTON (COM A+/START)
DIP 6 ON =>
It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF =>
Opens the gate when closed. There is no effect if activated while
opening. If activated when gate is open, the gate closes. If activated while
closing, the gate re-opens.
OPEN BUTTON (COM A+/OPEN)
The button controls the opening movement when the gate is stationary. If activated while
closing, it re-opens the gate.
B.I.O. BUTTON - OPENS WITH CLOCK FEATURE (COM A+/B.I.O.)
This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies in parking or residential areas and, temporarily, for moving operations).
By connecting a switch and/or a daily/weekly clock to COM A+/B.I.O., you can open and keep
the automation open for as long as the switch is pressed or the clock remains active. When
the gate is open, all the commands are ignored.
Releasing the switch or at the end of the set time, the automation closes immediately.
CLOSE BUTTON (COM A+/CLOSE)
Controls the closing movement when the gate is stationary.
TRANSMITTER
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the
gate reopens.
PEDESTRIAN OPEN BUTTON (COM A+/PED.)
Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any command
linked to the B2 24V board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the
gate reopens.
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELLS (COM A+/PHOT 1, COM A+/PHOT 2)
NOTE: the transit through the photocells is signaled by a buzzer tone
DIP 4 OFF => if an obstacle is placed in range of the photocells when the gate is closed,
the gate does not open. During operation, photocells work when opening
(by starting the opening movement only after the obstacle is removed) and
closing (by starting the reverse movement only after the obstacle is removed).
DIP 4 ON => if an obstacle is placed in range of the photocells when the gate is closed
and the command to open is given, the gate opens (the photocells do not
work while opening). Photocells work only during closing (with reverse motion
restored after a second, even if they are still engaged).
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply
is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal A -, to
shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
MONITORING OF PHOTOCELLS (A+ TEST A-)
35
G
B
24Vdc
Term.
A -

Publicité

loading

Ce manuel est également adapté pour:

Super 4000 iceSuper 4000 sqSuper 4000 ice sqL1/r2-crxAa31030Aa31032 ... Afficher tout