Télécharger Imprimer la page

Generac Power Systems SE 300 A Manuel Du Propriétaire page 8

Publicité

Les langues disponibles

Les langues disponibles

Installation
These instructions are for a typical air conditioner installation.
Control of heat pump and 2-stage air conditioners will require
special connections or the use of Power Management Modules
to control the loads.
Control of a Separate Contactor
A separate contactor relay module can be purchased from the manu-
facturer. This model is supplied in a 24 VAC (requires a starter kit,
which includes a field installed 24VAC transformer and the first 50
amp, 24V actuated module) or 120 VAC coil version.
1.
Mount the contactor module and connect the load to the main
contacts.
2.
Connect the contactor coil to the desired OPCB (contactor 1, 2,
3 or 4) terminals on the terminal strip.
3.
Connect additional Power Management Module contactors in a
similar fashion.
It will be necessary to determine the order of "shedding" the
connected loads and connect the loads to the OPCB in that
order. One is the highest priority and four is the lowest priority.
2.5.1 LOAD SHED SEQUENCE OF OPERATION
When configured for full functionality, six loads are organized into
four priority groups. Priority 1 (A/C 1) and the associated general use
contactor (Load 1) is the highest priority and is usually the first load(s)
reconnected (except in fast load shed mode). Priority 4 (Load 4) is the
lowest priority and is usually the last load reconnected (except in fast
load shed mode). The priority groups are as follows:
Priority Group 1
• A/C 1 and Load 1
Priority Group 2
• A/C 2 and Load 2
Priority Group 3
• Load 3
Priority Group 4
• Load 4
Since A/C is typically considered the most important, it is hardwired as
the two highest priority levels (A/C 1, A/C 2). Two other loads that may
be considered of equivalent importance are wired to the associated
general use contactors (Load 1, Load 2). Loads of lesser importance
are wired to the remaining contactors (Load 3, Load 4).
If the OPCB is fully functional and managing six connected loads,
and an event occurs which causes a load to increase beyond the
capacity of the generator, the OPCB identifies an overload condition
and instantly sheds all loads. After five minutes elapses, the OPCB
reconnects the loads associated with Priority Group 1 (A/C 1, Load 1),
and then reconnects the remaining loads at fifteen second intervals.
If the OPCB sees another overload while it is reconnecting loads, the
offending load is shed and locked out for 30 minutes. The next load
in the sequence is then reconnected. This process continues until all
loads have tried to reconnect (Figure 2.4).
6
NOTE:
NOTE:
Figure 2.4 — Standard Load Shed
Overload Condition - All Loads Shed
5
Minutes Elapses - Priority Group
15
Seconds Elapses - Priority Group
15
Seconds Elapses - Priority Group
15
Seconds Elapses - Priority Group
2.6
CONNECTION OF POWER SUPPLY FOR
CONTACTORS
The Overload Prevention Control Board (OPCB) can be powered from
either a 24 VAC or 120 VAC power supply. The 24 VAC supply is from
a class 2 transformer that can be purchased from the manufacturer.
Mounting holes are provided in the enclosure subplate for mounting of
the transformer. The 120 VAC supply is fused at 5 amps and is factory
connected to OPCB terminals labeled "T1 and "Neutral".
2.6.1 24 VAC SUPPLY
Transformer connection are made as shown in Figure 2.2 on page 7.
• Blue wire - OPCB "LOAD SUPPLY 1" terminal
• Black wire - OPCB "T1" terminal
• White wire - OPCB "NEUTRAL" terminal
• Yellow wire - OPCB "LOAD SUPPLY 2" terminal
2.6.2 120 VAC SUPPLY
Install the following jumpers on the OPCB module (Figure 2.3).
• Wire - Load Supply 1 to T1
• Wire - Load Supply 2 to T2
Load supply voltage on the OPCB terminals
must match the PMM contactor coil voltage, or
the equipment will be damaged.
Figure 2.3 — 120 VAC Supply Connections
1
Reconnected
2
Reconnected
3
Reconnected
4
Reconnected

Publicité

loading

Ce manuel est également adapté pour:

Se 400 a