Installation Instructions - Artidor AR-051 Série Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

gas, mist or vapor is T3 for the outdoor / condenser unit and T4 for the indoor / evaporator
unit. The AR-051 air conditioning system is suitable for ambient temperatures of -27 °C up to
+52 °C.
II 3 G Ex ec h ic mc IIC T3 Gc
Type: AR-051/0311 C
Cert. ARTIDOR 20ATEX9999
TF & Serial No.: AS201234
ARTIDOR Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.artidor.com
Example of an outdoor unit label
II 3 G Ex ec h ic IIC T4 Gc
Type: AR-051/0711
Cert. ARTIDOR 20ATEX9999
TF & Serial No.: AS201234
ARTIDOR Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.artidor.com
Example of an indoor unit label
7.

Installation instructions

General
Installation of explosion-safe equipment such as this product must be carried out by
personnel specially trained and qualified to do this, following the relevant requirements
of the installation standard EN 60079-14.
For the installation and use of this product the relevant safety regulations and also the
generally recognized latest state of the technology apply. Also follow the national
regulations and legal requirements relating to electrical connections to the electricity
grid.
Isolate power prior to installation.
Installation manual AR-051 explosion-safe air conditioning systems
ARTIDOR
220 – 240 VAC 50 Hz
220 VAC 60 Hz
1.920 Watt
Year: 2020
ARTIDOR
220 – 240 VAC
50 Hz
40 Watt
Year: 2020
E
01-2020
7 / 40

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ar-051/0311 cAr-051/0711

Table des Matières