Setting The Detector; Dip Switch Sw1; Dip Switches; Configuring The Coverage Pattern - Aritech DD1012 Fiche D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18

Setting the detector

See Figure 14 for jumpers and DIP switch location.
Jumpers
Jumpers set onboard EOL mode and value. The circuit is
shown in Figure 11.
JA: Set onboard alarm EOL resistor (Ra)
1 kΩ
4.7 kΩ (factory
default)
Off: No onboard alarm EOL.
JT: Set onboard tamper EOL resistor (Rt)
1 kΩ
4.7 kΩ (factory
default)
Off: No onboard tamper EOL.
Configuring the zone
To set up the zone, apply the following guidelines.
Select appropriate EOL resistor values with JA and JT.
For example, setting of jumper JT determines Rt value.
For isolated outputs remove JT.
Remove jumpers JA and JT to exclude onboard EOL
values.
For a single zone with all onboard resistors set, the zone
resistance can be the following.
Table 2: Zone resistance values
Zone state
Value
0 Ω
Tamper (short)
Normal
Rt
Alarm
Rt+Ra
Tamper (open)

DIP switches

Table 3: SW1, general settings
Switch
Values
6: LED
On: LED on*
5: Remote
On: Remote on
4: Reserved
3: Polarity
On: Positive polarity
1, 2: Radar
1 On, 2 On: 12 m (39 ft.)*
range
1 Off, 2 On: 9 m (30 ft.)
*
Factory default
P/N 146550999-1-ML • REV R • ISS 20JUL22
2.2 kΩ
5.6 kΩ
2.2 kΩ
5.6 kΩ
Default
0 Ω
4.7 kΩ
9.4 kΩ
Off: LED off
Off: Remote off*
Off: Negative polarity*
1 On, 2 Off: 6 m (20 ft.)
1 Off, 2 Off: 4 m (13 ft.)

DIP switch SW1

SW1-1, SW1-2: Radar range
Use SW1-1 and SW1-2 to set the radar range exactly to fit the
application. The radar is of a range-gating type which means
that the range of detection is very accurate.
4 m (13 ft.)
6 m (20 ft.)
SW1-3: Polarity
On: Positive polarity. Configures the inputs (WT and D/N) as
"Active high".
Off: Negative polarity. Configures the inputs (WT and D/N) as
"Active low". Factory default.
The functionality is explained in Figure 10.
Figure 10
(1) Polarity high
(2) Polarity low
This function also depends on the SW1-5 setting. See "SW1-5:
Remote functionality" below.
SW1-4: Reserved
Do not change.
SW1-5: Remote functionality
On: Remote on. Enables WT and day/night inputs.
Off: Remote off. Disables WT and day/night inputs (factory
default).
The following functionality depends on the Remote setting.
Table 4: Functions dependent on the Remote setting
Item
Description
SW1-5 Remote on SW1-5 Remote off
SW1-3
Polarity
Selectable
WT
WT input
Enabled
D/N
D/N input
Enabled
Other
Green Mode
Enabled in day
mode with no WT
Enabled in day
Alarm memory
mode with no WT
See also "Connections" on page 4.
SW1-6: LEDs
On: LEDs are enabled. See "LEDs and outputs" on page 6 for
LED functionality.
Off: LEDs are disabled for any state.

Configuring the coverage pattern

Remove blinders (Figures 8 and 9) if necessary. The
modified pattern is shown below blinder configuration.
Note:
If both blinders are installed in DD1012(-D), the
detector range is limited to 6 m (default) .
In case of DD1012(-D), modify the pattern by breaking out
blinder parts (shown as gray in Figure 8, item 1). The
9 m (30 ft.)
12 m (40 ft.)
Factory default.
(3) Walk test
(4) Day/night
Positive only
Disabled
Disabled
Disabled
Disabled