Basic Configuration; Inputs And Outputs - AKO 16624 Guide Rapide

Contrôleur de température et d'humidité pour chambre froide
Masquer les pouces Voir aussi pour 16624:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Basic configuration

Description
B00
Delay of all functions on receiving power supply
Bcn
B01
Cold room light timing
Function of password
B10
1=Block access to parameters
PAS
Access code (Password)
B20
MODBUS address
Communication speed:
B21
B22
Acoustic alarm enabled 0= No 1=Yes
Lower display function 0=Shows moisture 1=Shows the time (1)
B23
2=Shows moisture and the time alternately (1)
UNT
Work units
EP
Exit to level 1

Inputs and outputs

Description
In0
Connected probes 1=Probes S1 and SH (Cold room temperature + moisture)
I00
2=Probes S1, S2 and SH (Cold room temp. + evaporator temp. + moisture)
Configuration of digital input 1
0= Deactivated
I10
3=Severe external alarm
5=Low pressure switch
Polarity of the digital input 1
I11
0=Activates on closing contact; 1=Activates on opening contact
Configuration of digital input 2
I20
1=Door contac
4= Temp. control selector / temp. + moist.
Polarity of the digital input 2
I21
0=Activates on closing contact; 1=Activates on opening contact
Configuration of input 3
1=Door contac
I30
4=Temp. control selector / temp. + moist.
6=Product temperature (HACCP alarm control)
Polarity of the input 3
I31
0=Activates on closing contact; 1=Activates on opening contact
Configuration of relay AUX1 0=Deactivated 1=Compressor/Resistor sump
O00
2=Light
4=Same status as COOL relay
* According to wizard.
0=Inactive
2=Block keypad
0=9600 bps
1=19200 bps
2=38400 bps 3=57600 bps
0=ºC
1=ºF
1=Door contact
4=Temp. control selector / temp. + moist.
0= Deactivated
2=External alarm
3=Severe external alarm
5=High pressure switch for Hot Gas
0= Deactivated
2=External alarm
3=Severe external alarm
5=Log temperature
3=Virtual control
5=Same status as unit
(1) Only available with the CAMM module installed.
22 22
Values Min.
Min.
Min.
bps
Values Min.
2=External alarm
1662H411 Ed.06
Def. Max.
0
0
255
0
0
999
0
0
2
0
0
99
1
1
247
0
0
3
0
1
1
0
0
2
0
0
1
Def. Max.
1
2
2
*
0
5
*
0
1
*
0
5
*
0
1
0
3
6
0
0
1
*
0
5